Eclipse TFB, V2, Installation Guide 310, 11/14/2014

Adjust the Nozzle

NOTE:

 Place burner on a suitable working surface.

1. Remove the spark rod (3) or (3a) and flame rod (3) if

applicable.

2. Remove the four washers and bolts (1).

3. Pull the rear cover (2) far enough away from the

housing (4) to get access to the lock nut (5).

4. Loosen the lock nut (5).

5. Push the assembly back together.

6. Hold the rear cover (2) in position and screw the

nozzle in or out to adjust dimension A. See Figure 3.1.

7. Carefully pull the rear cover (2) and nozzle assembly

out of the housing (4).

Figure 3.2. Disassemble the Burner

Figure 3.3. Adjust the Nozzle

8. Turn the nozzle (6) over the shortest distance until the

opening (7) in the nozzle for the spark rod (3) aligns
with the appropriate opening in the rear cover (2).

9. Make sure that the nozzle (6) does not move and

tighten the lock nut (5).

10. Reinstall spark rod (3) or (3a) and flame rod (3) if

used.

Figure 3.4. Position the Spark Rod &

Flame Rod (if used)

Table 3.2 Dimension A Inches (mm) for TFB075

Fuel

301k-350k

351k-400k

401k-500k

501k-600k

601k-750k

Natural Gas

0.374 (9.5)

0.500 (12.7)

0.500 (12.7)

0.625 (15.9)

0.625 (15.9)

Propane

0.251 (6.4)

0.374 (9.5)

0.374 (9.5)

0.500 (12.7)

0.500 (12.7)

Butane

0.125 (3.2)

0.251 (6.4)

0.251 (6.4)

0.374 (9.5)

0.374 (9.5)

Table 3.3 Dimension A Inches (mm) for TFB200

Fuel

751k-800k

801k-900k

901k-1000k

1001k-
1100k

1101k-
1200k

1201k-
1300k

1301k-
1400k

Natural Gas

0.500 (12.7) 0.500 (12.7) 0.500 (12.7) 0.625 (15.9) 0.625 (15.9) 0.625 (15.9) 0.625 (15.9)

Propane

0.374 (9.5)

0.374 (9.5)

0.374 (9.5)

0.500 (12.7) 0.500 (12.7) 0.500 (12.7) 0.500 (12.7)

Butane

0.251 (6.4)

0.251 (6.4)

0.251 (6.4)

0.374 (9.5)

0.374 (9.5)

0.374 (9.5)

0.374 (9.5)

Fuel

1401k-
1500k

1501k-
1600k

1601k-
1700k

1701k-
1800k

1801k-
1900k

1901k-
2000k

Natural Gas

0.625 (15.9) 0.625 (15.9) 0.625 (15.9) 0.625 (15.9) 0.625 (15.9) 0.625 (15.9)

Propane

0.500 (12.7) 0.500 (12.7) 0.500 (12.7) 0.500 (12.7) 0.500 (12.7) 0.500 (12.7)

Butane

0.374 (9.5)

0.374 (9.5)

0.374 (9.5)

0.374 (9.5)

0.374 (9.5)

0.374 (9.5)

Spark rod location if
flame rod is used.

3a

5/8” (16 mm)

3a

Spark rod location if
flame rod is used

Summary of Contents for TFB030

Page 1: ...TFB030 075 TFB200 Eclipse Tube Firing Burners Models TFB030 TFB075 TFB200 Version 2 11 14 2014 Installation Guide 310...

Page 2: ...and Eclipse will not be liable for any other injury loss damage or expenses whether direct or consequential including but not limited to loss of use income or damage to material arising in connection...

Page 3: ...er Installation 9 Checklist After Installation 11 Prepare for Adjustment 11 Adjustment Start Stop 12 Adjustment Procedure 12 Step 1 Reset the System 12 Step 2 Set High Fire Air 12 Step 3 Set Low Fire...

Page 4: ...F The recommended recuperators for the TFB are the Eclipse Bayonet Data 317 and the Bayonet Ultra Spec 318 Figure 1 1 TFB Audience This manual has been written for people who are already familiar with...

Page 5: ...by sanding sawing grinding cutting and other construction activities could release crystalline silica Crystalline silica is known to cause cancer and health risks from the exposure to these chemicals...

Page 6: ...matics in the System Design section to build your system Approval of Components Limit Controls Safety Equipment All limit controls and safety equipment must comply with all applicable local codes and...

Page 7: ...tability of the electrical power Type and supply pressure of the fuel Availability of enough fresh clean combustion air Humidity altitude and temperature of air Presence of damaging corrosive gases in...

Page 8: ...e 3 4 Position the Spark Rod Flame Rod if used Table 3 2 Dimension A Inches mm for TFB075 Fuel 301k 350k 351k 400k 401k 500k 501k 600k 601k 750k Natural Gas 0 374 9 5 0 500 12 7 0 500 12 7 0 625 15 9...

Page 9: ...s that stop the spark as soon as a signal is detected may prevent establishment of flame particularly when using UV scanners The flame monitoring control must maintain the spark for a fixed time inter...

Page 10: ...tion of recuperator shown shaded in Figure 3 8 with Moist PAK D by Fiberfrax Eclipse part 57325 DO NOT INSULATE THE BURNER The use of flexible nipples in hot air piping is strongly recommended to acco...

Page 11: ...rectly oriented relative to the gas or air flow Prepare for Adjustment After installation of the burner system components are complete the following steps should be followed in order to prepare for ad...

Page 12: ...tasheet for your particular burner to find the air pressure differential that you need at high fire This is now your target value for high fire NOTE A pressure tap is open when the screw inside the ta...

Page 13: ...m to low fire 2 Choose one burner in the zone Connect the manometer to tap A and tap B of the burner across the air orifice 3 Adjust the automatic zone air control valve until the low fire air pressur...

Page 14: ...l the burners have ignited then drive the zone air butterfly valve to high fire Make sure that the burners stay ignited Step 6 Set High Fire Gas 1 Use the gas curves on the appropriate datasheet to fi...

Page 15: ...spark rod or the ignition wire when the ignition is on You will get a shock Manual Ignition 1 Make sure the gas cock at each burner is closed 2 Start air blower 3 Drive the automatic zone air control...

Page 16: ...els in the exhaust every month If there is any change find the cause and correct it 7 View down the peepsights on the burners and down the exhaust legs of the tubes to check for unusual flame or carbo...

Page 17: ...wiring to the valve Check output from the flame safeguard Check solenoid valve coil for proper operation Replace if necessary Manual gas valve closed Open the gas valve Manual gas cock not open Open...

Page 18: ...g Check and clean filters spark rod and UV scanner If necessary After this step it is important that you clean the spark rod and UV scanner and make sure that there is no excessive soot on the nozzle...

Page 19: ...lectrical wiring Cannot initiate start sequence Air pressure switch has not made contact Check air pressure switch adjustment Check air filter Check blower rotation Check outlet pressure from blower H...

Page 20: ...er mm inch in 3 94 x 10 2 MJ Nm Btu ft standard 26 86 From To Multiply By kiloPascals kPa millibar mbar 10 meter m millimeter mm 1000 millibar mbar kiloPascals kPa 0 1 millimeter mm meter m 0 001 From...

Page 21: ...i...

Page 22: ...Installation Guide 310 11 14 2014 Eclipse Inc All Rights Reserved...

Reviews: