background image

9

Eclipse ThermJet Self-Recuperative, V5, Installation Guide 208, 2/4/2013

  Do not allow the ceramic combustor to carry the

weight of the burner or the combustor will break.

Figure 3.6

NOTE:

 The burner may require centering to assemble.

Nuts and bolts should be torqued to 15-20 ft-lbs (20-27
Nm) cold and re-torqued at operating temperature and
after 100 hours of operation. Position housing so air inlet
is oriented to align with the air manifold piping.

Step 5: Igniter

1. If already assembled, remove the rear cover

assembly by removing rear cover bolts. See Figure
3.9.

2. Thread igniter through rear cover and hole in nozzle.

See Figure 3.7 for burners without spark rod cooling
and Figure 3.8 for models with cooling.

NOTE:

 Do 

not

 apply any grease to the threads of the

spark plug. You can cause bad grounding of the spark
plug if you apply grease to it. Bad grounding of the spark
plug results in a weak spark. 

3. Slide the rear cover nozzle assembly through the air

inlet housing and into the combustor assembly. See
Figure 3.9.

4. Assemble the rear cover to the air inlet housing using

cap screws. Torque to 5 ft-lbs (7 Nm). Position cover
so gas inlet is aligned with gas manifold piping.

Figure 3.7

Figure 3.8

Figure 3.9

Step 6: UV Flame Sensing

1. Install the flame sensor into the designated opening in

the rear cover. See corresponding datasheet series
208 for proper location.

2. Make sure that the UV scanner is connected to the

electrical circuit of that burner.

  Connecting the UV scanner of a burner to the

electrical circuit of a different burner can cause
fires and explosions.

The UV scanner must be compatible to the flame
monitoring control that is used. Refer to the manual of
your selected control for proper selection of the scanner.

  Adjustments may vary from Eclipse published

values if the flame controls other than those
recommended in the Design Guide are used.
Consult with the engineer who specified the
alternate control for limitations.

CAUTION

CORRECT

WRONG

10 ± 2 mm

10 ± 2 mm

Spark rod cooling tube
should be flush with the nozzle

Rear Cover Nozzle

Assembly

Rear Cover

Bolts

Air

Inlet

Housing

DANGER

NOTICE

Summary of Contents for ThermJet TJSR0020

Page 1: ...Eclipse ThermJet Self Recuperative Burners Models TJSR0020 TJSR0100 Installation Guide 208 2 4 2013 Version 5 ...

Page 2: ... and Eclipse will not be liable for any other injury loss damage or expenses whether direct or consequential including but not limited to loss of use income or damage to material arising in connection with the sale installation use of inability to use or the repair or replacement of Eclipse s products Any operation expressly prohibited in this manual any adjustment or assembly procedures not recom...

Page 3: ...duction 6 Handling Storage 6 Position of Components 6 Approval of Components 6 Checklist Before Installation 7 Prepare the Burner 7 Furnace Wall Preparation 7 Burner Installation 8 Valves 10 Checklist After Installation 11 Prepare for Adjustment 11 4 Adjustment Start Stop 12 Introduction 12 Adjustment Procedure 12 Normal Operation Post Commissioning 15 5 Maintenance Troubleshooting 16 Introduction...

Page 4: ...burner system These aspects are Installation Use Maintenance Safety The audience is expected to be qualified and have experience with this type of equipment and its working environment Purpose The purpose of this manual is to make sure that you carry out the installation of a safe effective and trouble free system ThermJet Self Recuperative Documents Installation Guide No 208 This document Datashe...

Page 5: ...ts boards or gaskets Despite these efforts dust created by sanding sawing grinding cutting and other construction activities could release crystalline silica Crystalline silica is known to cause cancer and health risks from the exposure to these chemicals vary depending on the frequency and length of exposure to these chemicals To reduce the risk limit exposure to these chemicals work in a well ve...

Page 6: ...safety by an independent testing agency Typical application examples include American NFPA 86 with listing marks from UL FM CSA European EN 746 2 with CE mark from TuV Gastec Advantica Electrical Wiring All the electrical wiring must comply with all applicable local codes and or standards such as NFPA Standard 70 IEC60364 CSA C22 BS7671 Gas Piping All the gas piping must comply with all applicable...

Page 7: ...damaging corrosive gases in the air Prevent direct exposure to water Prepare the Burner Several components must be installed on a burner before it can operate Install the igniter in the burner before installing the burner See Step 5 Igniter and Flame Sensor Installation Furnace Wall Preparation Make sure the furnace wall is capable of supporting the weight of the burner to be installed If necessar...

Page 8: ...de exhaust tube through mounting extension flange into the furnace 3 Place gasket b against exhaust tube flange Use adhesive spray to hold gaskets in place See Figure 3 4 4 Gently place the adapter ring over the flange of the exhaust tube The recess on the adapter ring must face the exhaust tube flange The adapter ring should sit flush with the mounting extension 5 Bolt adapter ring to mounting ex...

Page 9: ...ir inlet housing and into the combustor assembly See Figure 3 9 4 Assemble the rear cover to the air inlet housing using cap screws Torque to 5 ft lbs 7 Nm Position cover so gas inlet is aligned with gas manifold piping Figure 3 7 Figure 3 8 Figure 3 9 Step 6 UV Flame Sensing 1 Install the flame sensor into the designated opening in the rear cover See corresponding datasheet series 208 for proper ...

Page 10: ...tial pressure measurements In addition there is a static air pressure tap that can be used to verify air pressure Valves Valve Orientation Install all the valves in such a way that the arrow if present on the valve body points in the direction of flow Figure 3 11 Valve Orientation Gas Cocks Make sure that the handle of a gas cock is at a right angle to the valve body when the valve is in the close...

Page 11: ...ower to rotate in the proper direction 5 Be sure all valves are installed in the proper location and correctly oriented relative to the flow direction Prepare for Adjustment After installation of the burner system components is complete the following steps should be followed in order to prepare for adjustment 1 Set the air pressure switch so that it drops out at 4 w c 10 mbar below the pressure ra...

Page 12: ...t gas would exit through an auxiliary flue with furnace pressure control The datasheet provides the Eductor butterfly valve settings to be used for both methods and different chamber temperatures Set the integral butterfly valve to the appropriate position for the desired chamber temperature and exhaust requirement See the appropriate datasheet in series 208 To adjust the integral butterfly valve ...

Page 13: ...plicable 1 Set the system to low fire 2 Connect the manometer to Taps A and C air orifice pressure differential 3 Adjust the minimum setting at the automatic zone air control valve until the low fire air differential pressure between taps A and C matches the Minimum Low Fire Air Pressure Drop in the datasheet This is the initial setting only Further adjustment may be required 4 Repeat steps 2 and ...

Page 14: ...ecked at high fire Check the air differential pressure tap A to C If necessary adjust the valve to achieve the desired pressure On multi burner systems check the differential pressure A to C on all burners If the difference in pressure is greater than 0 5 w c 1 25 mbar it will be necessary to adjust the air balance using the valve Check the differential gas pressure tap B to D at each burner if ne...

Page 15: ... fires and explosions Do not touch the ignition plug or the ignition wire when the ignition is on You will get a shock Stop Procedure 1 Close the following valves The manual gas cock for each burner or zone The manual gas cock at the main control valve All the manual shut off valves in the gas line upstream of the burner gas cock 2 Let the burners cool down Keep the blower on until the chamber tem...

Page 16: ...signals 5 Check ignition spark plugs 6 Check valve motors and control valves for free smooth action and adjustment 7 Check for proper operation of the ventilating equipment 8 Test the interlock sequence of all safety equipment manually make each interlock fail noting that related equipment closes or stops as specified by the manufacturer 9 Test flame monitoring control system by manually shutting ...

Page 17: ...er Restore power to the ignition transformer Check flame monitor controller No ignition Open circuit between the ignition transformer and the spark plug Repair or replace the wiring and connectors to the spark plug Check ground connection to the transformer No ignition The spark plug needs cleaning Clean the spark plug No ignition The spark plug is not correctly grounded to the burner Clean the th...

Page 18: ...e burner is erratic and does not respond to adjustment Flame signal weak Check condition of flame monitoring device Internal damage to the burner Some parts inside the burner may be loose or dirty Contact your Eclipse Combustion representative or the Eclipse factory The burner is unstable or produces soot or smoke The air gas ratio is out of adjustment Measure all the gas pressures and air pressur...

Page 19: ...ter mm inch in 3 94 x 10 2 MJ Nm Btu ft standard 26 86 From To Multiply By kiloPascals kPa millibar mbar 10 meter m millimeter mm 1000 millibar mbar kiloPascals kPa 0 1 millimeter mm meter m 0 001 From To Multiply By actual cubic foot h acfh actual cubic meter h am h 2 832 x 10 2 standard cubic foot h scfh normal cubic meter h Nm h 2 629 x 10 2 degrees Fahrenheit F degrees Celsius C F 32 x 5 9 pou...

Page 20: ...Installation Guide 208 2 4 2013 ...

Reviews: