Air Source Heat Pump EAP range user manual - www.ecoairpump.co.uk
Jumpers 5, 6,7 and 8 are used to set Duty/Assist Unit No.
JP8
JP7
JP6
JP5
Unit
0
0
0
0
No. 1 ( Duty)
0
0
0
1
No. 2 (Assist)
0
0
1
0
No. 3 (Assist)
0
0
1
1
No. 4 (Assist)
0
1
0
0
No. 5 (Assist)
0
1
0
1
No. 6 (Assist)
0
1
1
0
No. 7 (Assist)
0
1
1
1
No. 8 (Assist)
1
0
0
0
No. 9 (Assist)
1
0
0
1
No. 10 (Assist)
X
X
X
X
Invalid
14.3. Control Panel
ON/OFF
Press
ON/OFF
to switch on/off the unit.
MODE
Press
MODE
to select the running mode.
Mode selection is valid only when the compressor is off.
Cooling Mode: the unit will cool the water till the water temperature reaches the set point.