V&T Technologies Co., Ltd.
http://www.ecodrivecn.com
Chapter 5 List of Parameters
44
Function
code
number
Function code
name
Factory
setting
Setting range
Unit
Property
Function code selection
User
setting
process close loop control;
3: Composite control;
Vector control 2 without
encoder speed feedback:
4: Process open loop control
5: Analog value feedback
process close loop control;
6: Single phase pulse feedback
process close loop control;
7: Composite control;
P0.04
Open loop main
reference mode
0
0 ~ 4
/
×
0: Open loop digital frequency
reference (P0.05);
1: AI1 analog value reference;
2: AI2 analog value reference;
3: AI3 analog value reference;
4: DI pulse reference
P0.05
Open loop digital
frequency reference
50.00
0.00 ~ 300.00 Hz
○
Upper / lower frequency limit
(P0.13 ~ P0.14)
P0.06
Running command
reference mode
0
0 ~ 2
/
○
0: Operation panel;
1: Terminal;
2: Host computer
P0.07
Running direction
command
0
0 ~ 1
/
○
0: Run forward; 1: Run reverse
P0.08
Acceleration time 0 6.0
0.1 ~ 3600.0
s
○
15kW and below
0.1 ~
3600.0s
P0.09
Deceleration time 0 20.0
18.5kW and above
P0.10
S-curve time
0.0
0.0 ~ 3600.0
s
○
0.0 ~ 3600.0s
P0.11
Maximum output
frequency
50.00
0.01 ~ 300.00 Hz
×
Upper frequency limit P0.13 ~
300.00Hz
P0.12
Maximum output
voltage
380
1 ~ 480
V
×
1 ~ 480V
P0.13
Frequency upper
limit
50.00
0.00 ~ 300.00 Hz
×
Lower frequency limit P0.14 ~
Maximum output frequency
P0.11
P0.14
Frequency lower
limit
0.00
0.00 ~ 300.00 Hz
×
0.00Hz ~ Upper frequency limit
P0.13
P0.15
Basic operating
frequency
50.00
0.00 ~ 300.00 Hz
×
0.00Hz ~ Maximum output
frequency P0.11
P0.16
Torque boost
0.0
0.0 ~ 30.0
%
×
0.0: Auto torque boost;
0.1% ~ 30.0%
Group P1 Main and Auxiliary Reference Parameter
P1.00
Open loop auxiliary
reference mode
0
0 ~ 4
/
×
0: None
1: AI1; 2: AI2; 3: AI3; 4: DI
P1.01
Open loop reference
main and auxiliary
relation calculation
0
0 ~ 5
/
×
0: Main
+
Auxiliary;
1: Main - Auxiliary;
2: Auxiliary-50%;
3: Main
+
Auxiliary-50%;
4: Take maximum value;
5: Take minimum value
P1.02
Analog feedback
close loop control
main reference
mode
0
0 ~ 4
/
×
0: Digital voltage reference
P8.00;
1: AI1; 2: AI2;
3: AI3; 4: DI
P1.03
Analog feedback
close loop control
auxiliary reference
mode
0
0 ~ 4
/
×
0: None;
1: AI1; 2: AI2;
3: AI3; 4: DI
P1.04
Analog feedback
close loop control
reference main and
0
0 ~ 5
/
×
0: Main + Auxiliary;
1: Main - Auxiliary;
2: Auxiliary-50%;
3: Main + Auxiliary-50%;