49
Figure 33
For the acoustic alarm signal via the integrated buzzer, three different priorities can be set for each of the four alarm
triggers (low battery, low temperature, reception failure, external alarm).
These priorities are as follows:
• Priority 0:
No acoustic alarm
• Priority 1:
Acoustic alarm only during the day from 8 am to 11 pm
• Priority 2:
The acoustic alarm always occurs, regardless of the time of day
Ö
The default setting for the alarm triggers ‘battery’, ‘low temperature’ and ‘reception failure’ is ‘Priorität 1’
(= ‘Priority 1’), for the external alarm it is ‘Priorität 0’ (= ‘Priority 0’).
To change the priorities, proceed as follows:
• Briefly press the ‘
x
’ button once.
• Select ‘Sonderfkt.’ (special function) using the scroller.
• Briefly press the ‘
x
’ button once.
• Select ‘Konfig.’ (configuration) using the scroller.
• Briefly press the ‘
x
’ button once.
• Select ‘Alarmprio.’ (alarm priority) using the scroller.
• Briefly press the ‘
x
’ button once.
• The following information is displayed:
Figure 34
• Use the scroller to select the desired priority for the low temperature alarm.
• Briefly press the ‘MAKRO’ button once.
• The following information is displayed:
Figure 35
FHT 8W Heat Demand Relay
Installation and User Guide
Product Code EHC-FH06
1