Mounting and operating instructions
6.1
Inverse application
Attention:
The starting delay TDelay must be > 0 s and the relieving force during unlocking FDelay
must be adjusted in accordance.
Software configuration:
• Activate the parameter Inverse.
Attention: the motor connector must not be plugged in the same manner as for the standard
drive mechanism.
• The electric lock must be unlocked without mains power or powered by an external source.
• For installations without an electric lock, the interlocking force Fch must be programmed.
• If there is no electric lock and the interlocking force Fch is not adjusted, error 14/02 will be
displayed as a warning after the teach-in procedure. This means that the door leaf will endlessly
re-open.
Starting-up and teaching:
• The door leaf is closed at super-slow speed. The safety sensory system is active (except during
the teach-in procedure).
• Start the teach-in from the open position: This ensures the teach-in of the necessary current for
the possible angle between the mechanical open stop piece and the programmed open positi
-
on Ao.
• Closing sequence control: During start-up and teach-in the door leaves are synchronized (in
order to avoid a possible collision). The installation is only ready for operation as soon as both
door leaves are closed respectively after the teach-in procedure has been completed.
Note:
A renewed setting-up procedure (Teach) is required if:
• the spring tension has been changed
• the leaf weight has been changed
• the type of rod assembly has been changed
• the opening angle Ao has been changed
• the Teach has been obstructed before reaching an opening angle of 20°
• the distance between axles (dAxis) has been changed
• the parameter Invers has been changed.
Additional parameter and menu navigation
see chapter 7.4.