ETS 73
0548-990-51---60g_2019.10.indd
0548-990/52g
Page 79 of 98
Mounting and operating instructions
9.1.6
Options
9.1.5
System
9.1.7
Closing sequence / Interlock function
No.
Description
Cause
Elimination
Checking time
Reaction
E50
01...99
System error
Unexpected hard
-
ware or software
event.
Switch the drive mechanism off/on.
Carry out a Factory Reset, carry out a Software Update,
inform the manufacturer.
Permanent.
W or H or F
E51
01...99
E52
01...99
No.
Description
Cause
Elimination
Checking time
Reaction
E60
00
Relay PCB 0
Option PCB has been remo
-
ved, its address changed or
become defective.
Check if the option is provided.
If defective: Replace or remove from the configu
-
ration.
Note:
Deleting of error 60
see chapter 13.8.1.
Permanent.
W
10
Relay PCB 1
Permanent.
W
20
Relay PCB
Permanent.
W
30
Fire-protection PCB
Permanent.
A
No.
Description
Cause
Elimination
Checking time
Reaction
E70 xx CAN bus setting
CAN address xx existing
twice.
Correctly define the role of the closing sequence or the
interlock function.
Permanent.
W
E71
01
CAN connection
No CAN connection.
Plug in, check or replace the CAN cable.
Check if all the CAN participants are switched on.
Permanent.
W