Mounting and operating instructions
5.4.2
Motorized lock with own evaluation control
The motorized lock is equipped with an own evaluation control (either integrated or external).
The swing door drive mechanism is configured as the Master unit and transmits a voltage free
impulse for control unit of the motorized lock for relasing the latter. The electric power is supplied
directly via the swing door drive mechanism (i.e. the motorized lock does not require its own
power pack).
Note:
Remove the jumper between terminals 28 and 29 on the control PCB of the swing door
drive mechanism.
Designations
Terminals
Remarks
Swing door drive mechanism 1
24 VDC
3
GND
29
EL-COM
30
EL-NO
28
GND
32
EL-Fb
-
G-U BKS B
1956/1959
13
14
-
9
5
6
CONFIG
EL-Fb = N.C.
For obtaining a motorized daily release,
the seal as well as the board immediately
behind it must be pierced and the lock
must be restarted.
Attention:
Daily release is not allowed for
fire safety doors!
Connect terminals 1 and 29 on the swing
door drive mechanism.
G-U/BKS Secury
Automatic
1
brown
2
grey
-
3
black
-
-
Connect terminals 1 and 29 on the swing
door drive mechanism.
With fire safety doors, it is compulsora to
use an external power supply.
Effeff 509X/529X with con
-
trol unit 509XSTRG (EA420)
or
Abloy EL520 with control
unit 509XSTRG (EA421)
1
2 / 12
18
16
-
13
CONFIG
EL-Fb = N.O.
Schüco motor unit for Safe
-
Matic and InterLock
white
brown
-
green
-
-
Connect terminals 1 and 29 to swing on
the swing door drive mechanism.
Dorma SVP 2000 with con
-
trol unit SVP-S 2x (LON)
X5 / 1
X5 / 3
X3 /
⊥
X3 / IN1
X8 / C
X8 / NO CONFIG
EL-Fb = N.O.
PARAMETER
TDelay = 0
Attention:
For fire safety doors, it is com
-
pulsory to use module SVP-PR12!
Dorma M-SVP 2000 DCW
Dorma M-SVP 2200 DCW
Control unit SVP-S3x DCW
X1 / 1
X1 / 3
X5 / 3
X5 / 28
X8 / 34 X8 / 33
CONFIG
EL-Fb = N.C.
PARAMETER
TDelay = 0