DESCRIPTION OF THE CONTROL PANEL OF THE BURNER

3

2

1 -  reset key

2 -  working lamp

3 -  main switch I / O

4 -  high-low flame switch (PAB)

0

I

I

II

4

1

MAINTENANCE

YEARLY INSPECTION

Periodic inspection of the burner (combustion head, electrodes, etc.) must be carried out by authorised personnel once

or twice a year, depending of use. Before carrying out maintenance inspection on the burner, it is advisable to check its

general condition and carry out the following operations:

- Disconnect the burner from the power supply (remove the plug). 

- Close the gas cock.

- Remove the burner cover, clean the fan and air intake.

- Clean the combustion head and check the position of the electrodes.

- Re-assemble the parts.

- Check the seal on the gas pipe fittings.

- Check the flue.

- Restart the burner.

- Check the combustion parameters (CO

2

= 9.5 to 9.8),(CO = less than 75 ppm)

BEFORE EACH INTERVENTION CHECK;

- That the system is supplied with power and the burner connected.
- That the gas pressure is correct and the gas cock open. 
- That the control systems are correctly connected.
If all these conditions are present, start the burner by pressing the release button. Check the burner cycle.

THE BURNER WILL NOT START;

- Check the switch, thermostats, motor, gas pressure.

THE BURNER PREVENTILATES AND LOCKS AT THE END OF THE CYCLE:

- Check the air pressure and fan.
- Check the air pressure switch.

THE BURNER PREVENTILATES AND WILL NOT IGNITE:

- Check the assembly and position of electrodes.
- Check the ignition cable.
- Check the ignition transformer.
- Check the safety devices.

THE BURNER STARTS UP AND LOCKS AFTER THE SAFETY TIME LIMIT: 

- Check that the phase and neutral wires are correctly connected.
- Check the gas electrovalves. 
- Check the position of the detection electrode and its connection.
- Check the detection electrode.
- Check the safety devices.

THE BURNER STARTS UP AND LOCKS AFTER RUNNING FOR A FEW MINUTES.

- Check the pressure regulator and the gas filter.
- Check the gas pressure with an ammeter.
- Check the detection value (min 1,5 µA Landis).

EN

420010318203  

Max Gas 350 - 500 P/P AB 

25

Summary of Contents for MAX GAS 350 P AB

Page 1: ...X GAS 350 P AB MAX GAS 500 P MAX GAS 500 P AB Low Nox 420010318203 02 08 2011 BRUCIATORI DI GAS AD ARIA SOFFIATA BLOWN AIR GAS BURNERS BRULEURS GAZ A AIR SOUFFLE QUEMADORES DE GAS DE AIRE SOPLADO IT E...

Page 2: ...er and regulations Working of the burner p 17 Control box up cycle p 18 Adjusting air gas p 19 PAB minimal gas adjustment p 20 Air servomotor adjustment p 20 Regulating the combustion p 21 22 Adjustin...

Page 3: ...200 200 100 300 400 300 400 500 600 0 1 2 3 4 5 6 7 8 9 mbar kW kcal h x 1000 MAX GAS 350 P AB MAX GAS 500 P AB 500 WORKING FIELDS Output Backpressure in comb chamber OPERATING FEATURES Model Max Gas...

Page 4: ...o control that this last is perfectly sealed Also verify that the chimney is not obstructed Open the gas cock and carefully bleed the piping through the pressure gauge connector then check the pressur...

Page 5: ...d off disconnect the flame detection cable from relevant electrode so as to make the valve to automatically shut off at the ignition after the safety time Make a reading on the gas meter Start the bur...

Page 6: ...lays KL Low fire LK Air damper LKP Air damper position LP Air pressure switch LR Load controller M Fan motor R Control thermostat pressurestat SA Actuator STB Safety limit thermostat Si External pre f...

Page 7: ...stment of burner no fuel Faulty ignition equipment 3 blinks on LP faulty Loss of air pressure signal after t10 LP welded in normal position 4 blinks on Extraneous light when burner is started up 5 bli...

Page 8: ...for air damper position on burner s shutdown total close 0 II Adjusting cam ORANGE for opening position in ignition and Low Flame by the screwdriver III Adjusting cam RED for opening position in High...

Page 9: ...ng the combustion head figure to suit the power required as shown in figure 3 dose the gas by regulating the gas ramp see figure in the ramp manual Low flame setting 1 after regulating the maximum pow...

Page 10: ...in head 13 mbar Gas pressure in head Head position ADJUSTING THE AIR PRESSURE SWITCH The air pressure switch must be adjusted so that an insufficient air flow does not allow the CO value to exceed 1...

Page 11: ...C microammeter with a 0 50 or 0 100 A dial When the burner is run ning and is properly adjusted the value read must be steady and never be smaller than 1 5 A LME 11 21 22 LANDIS LME11 LME21 22 min 1 5...

Page 12: ...13 14 15 16 7 7 7 8 9 10 11 12 EN 420010318203 Max Gas 350 500 P P AB 24...

Page 13: ...urner connected That the gas pressure is correct and the gas cock open That the control systems are correctly connected If all these conditions are present start the burner by pressing the release but...

Page 14: ...ING SWITCH INTERRUTTORE DI LINEA ER ELETTRODO DI RIVELAZIONE IONISATION PROBE ELECTRODE D IONISATION ELECTRODO DE IONIZACION ELETTROVALVOLA GAS GAS SOLENOID VALVE ELECTROVANNE GAZ ELECTROVALVULA DE GA...

Page 15: ...XTRA SAFETY GAS SOLENOID VALVE ELETTROVALVOLA GAS DI SICUREZZA ELECTROVANNE GAZ DE SECURITE SAFETY THERMOSTAT THERMOSTAT DE SECURITE TERMOSTATO DE SEGURIDAD TERMOSTATO DI SICUREZZA TERMOSTATO CALDERA...

Page 16: ...ri SERVOMOTOR FLAME SENSOR S p A ECN FIRST CREATION BY TERM LAWS WE RESERVED THE PROPERTY OF THIS WIRING DIAGRAM WITH PROHIBITION OF USE AND REPRODUCTION LEAKAGE CONTROL CONTROL BOX DATE ECN MODICATIO...

Page 17: ...PRESSION MIN GAS PRESSURE SWITCH MIN PRESSOSTATO GAS DI MINIMA SAL FUSIBILE FUSE FILTRE ANTIPARASITES MAIN SWITCH WITH FUSE ANTJAMMING FILTER FILTRO ANTIDISTURBO FILTRO DE PROTECION ANTIDISTURBIO INTE...

Page 18: ...flam Bruciatori SERVOMOTOR FLAME SENSOR S p A ECN FIRST CREATION BY TERM LAWS WE RESERVED THE PROPERTY OF THIS WIRING DIAGRAM WITH PROHIBITION OF USE AND REPRODUCTION LEAKAGE CONTROL CONTROL BOX DATE...

Page 19: ...MMING FILTER FILTRO ANTIDISTURBO FILTRO DE PROTECION ANTIDISTURBIO INTERRUPTOR GENERAL CON FUSIBLE INTERRUPTEUR GENERAL AVEC FUSIBLE INTERRUTTORE GENERALE CON FUSIBILE STC SPA STS FUSIBLE FUSIBLE MOTO...

Page 20: ...0 1 1 2 3 4 5 6 7 8 9 10 17 16 11 12 13 15 14 18 19 20 22 21 MAX GAS 350 P MAX GAS 500 P 23 24 25 27 28 26 29 30 31 32 33 34 35 36 350 P RU ES FR EN IT 420010318203 Max Gas 350 500 P P AB 68...

Page 21: ...1 I II 1 2 3 4 5 6 7 8 9 10 17 16 11 12 13 15 14 18 19 20 22 MAX GAS 350 P AB MAX GAS 500 P AB 25 350 P 21 23 24 27 28 26 29 30 31 32 33 34 35 36 37 RU ES FR EN IT 420010318203 Max Gas 350 500 P P AB...

Page 22: ...DE PRESSION SOPORTE ACCESO DE PRESI N 65324691 65324691 21 CABLE D IONISATION CABLE DE IONIZACION TC 65320946 65320946 TL 65320947 65320947 22 CABLE D ALLUMAGE CABLE DE ENCENDIDO TC 65320944 65320944...

Page 23: ...20 95 4 65324691 65324691 21 9 4 U 5 TC 65320946 65320946 TL 65320947 65320947 22 9 04 1 TC 65320944 65320944 TL 65324194 65324194 23 5 4 U 5 65320950 65320950 24 5 04 1 65324331 65324331 25 1 5 9 2 1...

Reviews: