background image

pag.16

techniques for energy saving

LB1360   

MULTICALOR 700.1÷1200.1 MD 

- Situation -

The number 

1999 blinks

in the display as the actual value, with the 

set point value displayed normally.

- Cause -

The real value is not being measured.  This means that the upper or lower

limit of the measurement range on analog input 1 (real value) has been exceeded. 

- Remedy -

Check the electrical connections and the state of the probe.  If the probe

is faulty, the regulator will not indicate the real value of the physical quantity 
monitored.  This will result in automatic shutdown (failsafe), 

deactivation of the

self-adapt function and inhibition of manual operation. 

The response of the 

auxiliary contact will depend on the configuration of parameter C113. 

- Situation -

The number 

1999 blinks

in the display as the actual value, with 

tA

showing in the set point field.

- Cause -

The external temperature is not being measured.  This means that the

upper or lower limit of the measurement range on analog input 3 (real value) has
been exceeded.

- Remedy -

Check the electrical connections and the state of the probe.  If the probe

is faulty, the regulator will not indicate the real value.

- Situation -

The number 

1999 blinks

in the display as the actual value, with 

SP .E

showing in the set point field.

- Cause -

The external set point value is not being measured. This means that the

upper or lower limit of the measurement range on analog input 2 (real value) has
been exceeded.

- Remedy -

Check the electrical connections and the external set point signal.  If the

probe is faulty, the regulator will not indicate the real value of the physical quantity
monitored. 

This will result in automatic shutdown (failsafe), deactivation of the 

self-adapt function and inhibition of manual operation.  

ERROR/FAULT INDICATION

NUMBERS BLINKING IN DISPLAY

Analog input 1 (actual value)

Pt1000, 2-wire, Landis & Staefa IEC 751 

5

FT-TP/… (passive probe)

Ni1000, 2-wire, Landis & Staefa

9

QAE2 … (passive probe - water probe)
Standard Signal DC 0…10 V QBE620P…
(active probe - pressure probe)

G

C111 – C112

INPUT CONFIGURATION INDICATIONS 

Analog Input 3 (external temperature)

No function (probe not active)

0

External probe Pt 1000, 2-wire,

1

QAC22 (passive probe)

AUXILIARY CONTACT, TYPE OF REGULATOR, SET POINT 

“SP1”

BLOCK 

C112.

Parameter configuration

Set point “SP1”

Set point SP1 - data input from keys

0

Set point SP1 - interlocked to external probe (configure)

1    

Summary of Contents for Multicalor 1000.1 MD

Page 1: ...S T E C LB1360 27 05 2004 Multicalor 700 1 MD Multicalor 800 1 MD Multicalor 1000 1 MD Multicalor 1200 1 MD Light oil Natural Gas 300 mbar MODELS techniques for energy saving GAS LIGHT OIL DUAL BURNE...

Page 2: ...500 2 000 2 500 2 700 kcal h 1 290 000 1 724 000 2 155 000 2 327 600 Max capacity Natural Gas Nm3 h 729 855 1 056 1 318 Min capacity Natural Gas Nm3 h 150 201 251 272 Max light oil flow rate kg h 613...

Page 3: ...carried out with the max air delivery the burner control circuit turns the air damper to the max delivery position by the air servocontrol in approximately 30 seconds time When the servocontrol is fu...

Page 4: ...rging the ignition tran sformer cuts in and generates a spark between the electrodes At the same time the two gas valves open Vs safety valve and Vl working valve The total safety in case of missed ig...

Page 5: ...m gas flow rate see figure on solenoid valve adjustments or adjust the gas pressure in the governor ADJUSTING THE MAXIMUM AIR FLOW RATE Adjusting the maximum air flow rate see figure detail 2 Loosen t...

Page 6: ...essure switch to the minimum by turning regulator D to position 1 Start the burner and keep in low flame running while checking that combustion is cor rect Through a small cardboard progressively obst...

Page 7: ...e motor s thermal protection When all the above mentioned conditions are checked and accomplished it is possible to go on with burner s tests Power the burner The control box feeds the ignition transf...

Page 8: ...ation That check valve is suitably designed for the duty The pump pressure is set at a value of 22 25 bar during the testing of burners Before starting the burner bleed the air in the pump through the...

Page 9: ...pag 9 LB1360 MULTICALOR 700 1 1200 1 MD techniques for energy saving...

Page 10: ...pag 10 techniques for energy saving LB1360 MULTICALOR 700 1 1200 1 MD...

Page 11: ...ation Before going on with the maintenance controls of the burner it should be advisable to check its general conditions according to the following steps Unplug the burner close the fuel cock shut dow...

Page 12: ...s are clogged Light oil pressure is too low Combustion air s flow rate too high related to nozzle output THE BURNER RUNS THE PREPURGING BUT DOES NOT IGNITE Check the position of the electrodes check t...

Page 13: ...educe power CLOSE 1st Stage Increase power OPEN 2nd Stage Two stage operation Description of display and keys on the RWF 40 microprocessor regulator The figure shows the normal display indicating the...

Page 14: ...e PGM PGM key to access the parameters level To move from one parameter to the next press PGM PGM When HYS1 is displayed burner ignition differential stage II increase or decrease the value using the...

Page 15: ...31 4 Cod S720 1 Connection for probe QAE2 passive probe Water probe Configuration code C111 9XXX Connection for probe FT TP passive probe Degusa probe Configuration code C111 5XXX Connection for probe...

Page 16: ...the probe is faulty the regulator will not indicate the real value Situation The number 1999 blinks in the display as the actual value with SP E showing in the set point field Cause The external set...

Page 17: ...or through the relative opening in the electrical panel A Insert the fixing anchors and screws into the slots and secure the unit to the panel B To open the regulator squeeze the cover from the ends a...

Page 18: ...ive probe active probe QBE620 P QAE22 FT TP 1000 P4 P10 P16 P25 P40 Analog input 1 2 and 3 setpoint changeover shift C111 9030 5030 G000 G000 G000 G000 G000 Limit comparator controller type setpoint 1...

Page 19: ...SA BEM43141 MULTICALOR 1000 1 MD LANDIS SQM 50 481A2 LANDIS LFL 1 622 DUNGS VDK 200 A UV 06 05 2004 FMP 95 96 KMP R S T NO Q HLB S1 R1 10 11 8 5 6 7 9 T1 N FMV 95 96 SAgG 1 2 3 0 SAMA 1 2 3 0 FMV 97...

Page 20: ...FETY THERMOSTAT SWITCH OIL GAS SAgG STS PRESSOSTAT AIR PRESOSTATO AIRE TERMOSTATO CALDAIA BOILER THERMOSTAT STC INTERRUPTOR GENERAL CON FUSIBLE INTERRUPTEUR GENERAL AVEC FUSIBLE MAIN SWITCH WITH FUSE...

Page 21: ...000 1 MD 4 8 9 39 28 29 33 37 38 57 3 1 5 42 31 30 32 2 6 10 11 53 54 0 15 30 45 60 75 90 0 I 0 AUTO 0 OIL GAS OIL GAS RESET 21 19 20 FIN D FIN D FIN DER FIN DER 13 7 12 15 16 17 18 K6 RWF 40 PGM PGM...

Page 22: ...4 E1510 23 FUSE SUPPORT FUSIT FH B528 E802 2 24 REL BASE Finder 5532 R905 Finder 5534 R906 25 REL Finder 5532 R711 Finder 5534 R712 26 TIMER AEG SDE R527 27 UV CELL LANDIS QRA 2 A205 28 IGNITION CABLE...

Page 23: ...pag 23 LB1360 MULTICALOR 700 1 1200 1 MD techniques for energy saving NOTE...

Page 24: ...principali Ecoflam S p A via Roma 64 31023 RESANA TV Italy tel 0423 715345 r a telefax 0423 715444 Italy 480009 Export 480873 715538 http www ecoflam it e mail ecoflam ecoflam it ECOFLAM S p A reserve...

Reviews: