pag.23
EN
420010243004 MULTICALOR 170.1-200.1 PR/PR
ADJUSTING THE INTERMEDIATE BURNER CAPACITY
Using the selector, start the servomotor (closing or opening) and position on 0 to stop the stroke; the adjustment is
made as outlined below. Repeat the operation for the other cam points.
Adjustment the intermediate gas flow rates (see figure, detail 3): - using a suitable Allen wrench, change the position of
the cam guide blade; if you screw it down, the flow rate is reduced; if you unscrew it, the flow rate increases.
SETTING THE FIRING HEAD
The firing head position adjustment is made in order to obtain the best combustion efficiency. When used with mini-
mum outputs the firing head is adjusted in rear position. With high output, the firing head is adjusted in forward posi-
tion.
Adjustment:
- Loosen screw A through a suitable Allen key.- By a screwdriver act on the hex. head screw B until is
reached the desired position. - Tighten screw A
REMOVING THE BLAST TUBE
–
+
B
A
+
--
REMOVING THE FIRING HEAD
The control of the detector current shall be carried out by plugging a microampe-
rometer with full scale at 1000 µA (D.C.) in series with the UV-cell. If the detec-
tor current is too low verify the connection between phase and neutral of the bur-
ner and the grounding of the burner itself. Minimum required detector current is
200 µA.
LME22
QRA
AGQ3.1A27
1
2
S
W
S
W
B
L
B
L
FLAME DETECTOR SYSTEM CHECK
SW = BLACK
BL = BLU
2
3
5
8
7
6
VgR
Vg
A
R
VgS
VG
VGS
1
4
LIGHT-OIL CIRCUIT
A -
HOSE
B -
OIL FILTER
C -
OIL COCK
1 -
PUMP
2 -
SAFETY OIL VALVE
3 -
OIL VALVE
4 -
RETURN OIL VALVE
5 -
NOZZLE
6 -
GAS PRESSURE SWITCH
7 -
SAFETY GAS VALVE
8 -
GAS VALVE
Suction
Return
A
A
B
C