background image

pag.7

techniques for energy saving

LB1203   

MULTICALOR 300.1÷400.1

AIR ADJUSTMENT

+

- -

Part. 1

Part. 2

Part. 3

-

+

-

COMMUTATORE

0

AUTO

 

0  = bloccaggio degli apparati per il 

 

      funzionamento in una posizione intermadia

 

   = funzionamento alla massima potenza 

 

   = funzionamento alla minima potenza

     AUTO  = funzionamento automatico

operating elements locked in an intermediate
position
operation on maximum capacity 
operation on minimum capacity  
automatic operation

SELECTOR

ADJUSTING THE MINIMUM CAPACITY OF THE BURNER – AIR and GAS

Position the selector placed on the control panel on position 2 and proceed as follows: 
Adjust the minimum gas flow rate using a suitable wrench, turn the butterfly valve until you reach the correct gas
flow, as established by analyzing the combustion process.

ADJUSTING THE MAXIMUM CAPACITY OF THE GAS

Position the selector, situated on the control panel, on position 1 and proceed as follows:
Adjusting the maximum gas flow rate (see figure on solenoid valve adjustments) or adjust the gas pressure in the
governor.

ADJUSTING THE MAXIMUM AIR FLOW RATE 

Adjusting the maximum air flow rate (see figure, detail 2). Loosen the nut holding the air damper transmission rod;
The correct air flow as established by analyzing the combustion process.

ADJUSTING THE INTERMEDIATE BURNER CAPACITY 

Using the selector, start the servomotor (closing or opening) and position on 0 to stop the stroke; the adjustment is
made as outlined below. Repeat the operation for the other cam points.
Adjustment the intermediate gas flow rates (see figure, detail 3): - using a suitable Allen wrench, change the position
of the cam guide blade; if you screw it down, the flow rate is reduced; if you unscrew it, the flow rate increases.

22 23

LANDIS

 

LFL 1.622

Fotocellula

min 70 

µ

A

Microamperometro 

fondo scala 1000 

µ

A

FLAME DETECTION SYSTEM CHECK 

PHOTORESISTOR

Microamperometer

full scale 1000 µA

Summary of Contents for Multicalor 300.1

Page 1: ...techniques for energy saving G A S T E C GAS LIGHT OIL DUAL BURNERS LB1203 24 10 2003 Multicalor 300 1 Multicalor 400 1 Light oil Natural gas 40 300 mbar MODEL...

Page 2: ...230 400 230 400 Motor kW 5 5 7 5 Motor s RPM N 2800 2800 Fuels Nat Gas LHV 35 9 Mj Nm3 8 570 kcal Nm3 Light Oil LHV 10 200 kcal kg max 1 5 at 20 C mbar 1500 2000 2500 3000 3500 4000 10 12 14 16 1000...

Page 3: ...tats close the leakage control device runs a valves leakage test then enables the burner to start the ignition cycle OPERATION OF BURNER WITH GAS MULTICALOR 300 1 400 1 Before starting the burner make...

Page 4: ...E PRESSURE REGULATOR The pressure regulator complete with its incorporated filter must be installed to avoid contaminants reaching the gas valve It is important to ensure certain conditions The pressu...

Page 5: ...justment gas output take out the cap L and loose the nut F Adjust the screw E with a screwdriver To reduce output turn counter clockwise to increa se it turn clockwise Tighten the nut F B The pressure...

Page 6: ...causes a drop in test pressure the device puts the system into the safety condition and the red pilot right on the device lights up The flame control device starts the burner fan to carry out prewash...

Page 7: ...r situated on the control panel on position 1 and proceed as follows Adjusting the maximum gas flow rate see figure on solenoid valve adjustments or adjust the gas pressure in the governor ADJUSTING T...

Page 8: ...pag 8 techniques for energy saving LB1203 MULTICALOR 300 1 400 1 REMOVING THE BLAST TUBE REMOVING THE FIRING HEAD FIRING HEAD SETTING...

Page 9: ...s up the ignition transformer and opens the light oil valve so the burner start the servomotor will set up to the light oil ignition position whilst the control box powers up the ignition transformer...

Page 10: ...UMP 1 2 5 6 3 4 1 INLET 2 RETURN 3 BLEED AND PRESSURE GAUGE PORT 4 VACUUM GAUGE PORT 5 PRESSURE ADJUSTMENT 6 TO NOZZLE SUNTEC TA3C40105 6 5 3 2 SUNTEC 1 4 SUNTEC J7CCC10014P NOZZLE PUMP PRESSURE bar G...

Page 11: ...the position of electrodes after having replaced the nozzle see illustration A wrong position could cause ignition troubles A pulsante di sblocco B operating lamps orange light oil green gas C Selecto...

Page 12: ...wn out The control box is faulty THE BURNER RUNS THE PREPURGING AND SWITCHES TO LOCKOUT AT THE END OF CYCLE Check the fan and the air pressure Check the air pressure switch Control box faulty Ignition...

Page 13: ...00 1 400 1 Multicalor 300 1 400 1 7 8 36 11 38 14 4 6 5 3 9 10 41 26 31 29 30 27 34 32 33 35 28 42 43 37 21 13 12 25 24 22 23 19 20 17 16 15 18 25 24 1 46 45 44 40 2 39 47 49 56 57 53 54 48 52 51 50 5...

Page 14: ...OIL SELECTOR R1020 5 R1020 5 21 SELECTOR R1020 5 22 LAMP Elettrospring EL N SC4 E1510 E1510 23 FUSE SUPPORT FUSIT FH B528 E802 2 E802 2 24 REL BASE Finder 5532 R905 R905 Finder 5534 R906 R906 25 REL F...

Page 15: ...PUMP MOTOR 740 W M147 M147 51 OIL VALVE Parker SCEM VE 140 V175 1 V175 1 52 COIL Parker SCEM VE 140 53 OIL VALVE DELTA 1 8 F F F84 V420 V420 54 COIL DELTA 1 8 F F F84 55 OIL FILTER 1 X1 7010 1 S103 1...

Page 16: ...GAS LIGHT OIL SELECTOR R1020 5 R1020 5 21 SELECTOR R1020 5 22 LAMP Elettrospring EL N SC4 E1510 E1510 23 FUSE SUPPORT FUSIT FH B528 E802 2 E802 2 24 REL BASE Finder 5532 R905 R905 Finder 5534 R906 R90...

Page 17: ...E Parker SCEM VE 140 V175 1 V175 1 52 COIL Parker SCEM VE 140 53 OIL VALVE DELTA 1 8 F F F84 V420 V420 54 COIL DELTA 1 8 F F F84 55 OIL FILTER 1 X1 7010 1 S103 1 X1 03 S107 5 56 GAS VALVE BRAHMA E6GSR...

Page 18: ...P 95 96 SAMA 1 2 3 0 FMV 95 96 SPA SPGmin HLG HLg YVg1 YVg2 YVgS pos 1 ALTA FIAMMA HIGH FLAME 2meALLURE ALTA LLAMA pos 3 AUTOMATICO AUTOMATIC AUTOMATIQUE AUTOMATICO INTERRRUPTEUR 2me 1re ALLURE pos 2...

Page 19: ...DE 1 LLAMA FIRST STAGE OIL SOLENOID VALVE ELECTROVANNE MAZOUT PETITE ALLURE ELECTROVALVULA DE GASOLEO 1 LLAMA YVg2 YVg1 YVG1 TELERRUPTOR MOTOR VENTILATOR CONMUTADOR GASOLEO GAS INTERRUPTEUR MAZOUT GAS...

Page 20: ...FIRMA DATA FIRMA CONTROLLATO DESCRIZIONE MODIFICA DISEGNATO DATA FIRMA COMUNICARE A TERZI IL CONTENUTO DEL PRESENTE A TERMINE DI LEGGE E VIETATO RIPRODURRE O CONTROLLO DI TENUTA APPARECCHIATURA UFF TE...

Page 21: ...DE 1 LLAMA ELETTROVALVOLA GAS DI PRIMA FIAMMA ELECTROVALVULA DE GASOLEO 2 LLAMA YVg2 YVg1 YVG1 REMOTE CONTROL SWITCH FAN MOTOR THERMOSTAT CHAUDIERE CONMUTADOR MANUAL AUTOMATICO INTERRUPTEUR MANUEL AU...

Page 22: ...pag 22 techniques for energy saving LB1203 MULTICALOR 300 1 400 1...

Page 23: ...pag 23 techniques for energy saving LB1203 MULTICALOR 300 1 400 1...

Page 24: ...principali Ecoflam S p A via Roma 64 31023 RESANA TV Italy tel 0423 715345 r a telefax 0423 715444 Italy 480009 Export 480873 715538 http www ecoflam it e mail ecoflam ecoflam it ECOFLAM S p A reserve...

Reviews: