- pag.4 -
LB1312
Oilflam 700.1-800.1 PR/MD
PUMP’S PRESSURE / OIL TEMPERATURE DIAGRAM
Pump inlet pressure:the vaporisation of light fraction of heated heavy oil causes premature pump wear, to
avoid this, use the inlet pressures shown in the graph.
1
2
3
4
5
0
6
50
100
150
bar
Oil temperature
C
°
Pump inlet pressure
CHECKS TO BE MADE TO ENSURE A PROPER INSTALLATION:
Before proceeding with the filling of the fuel system and subsequent burner start up, it is advisable to carry
out the following checks:
- Power line must be adequate to system’s adsorbed load
- Fuses must be adequate to the system’s load
- Boiler’s thermostats must have been properly connected
- Voltage and frequency must be within the specified limits
- Fuel type must be the one specified by the burner manufacturer
- Feed piping section must be adequate to the requested fuel flow rate
- Filters, cocks as well as fittings must have been properly installed
- Blast tube length must be the one specified by the boiler manufacturer
- Nozzle’s flow rate of the burner must be adequate to boiler’s output