![background image](http://html1.mh-extra.com/html/ecolab/elados-emp-ii-e60/elados-emp-ii-e60_operating-instruction_2354526118.webp)
417101438_EMPII_E60.docx
- 118 -
Rev. 11-02.14
10.3.16.2
Degas
PLUS
/ Degas strokes
Fig. 10.52 Configuration Degas
PLUS
/ Degas strokes
The number of strokes that
should be processed during a
degassing interval is recoded
under “degas strokes”.
Setting range: 1-100
Default setting = 0
10.3.16.3
Degas
PLUS
/ Degas break
The time between two degassing intervals is set under “degas break”.
If a metering request is submitted during this period, this is processed and the
Degas
PLUS
break time is reset and restarted.
Setting range:
hours
00 - 23
minutes
00 - 59
total
00.01 - 23.59h
Fig. 10.53 Configuration Degas
PLUS
/ Degas break
Default setting
= 00:00
10.4
Calibration
10.4.1 Overview
The procedure and display during the calibration process differ depending on whether or not
an oval gear meter is connected.
Fig. 10.54 Calibration Overview
Calibration pump:
•
see chapter
Calibration pump with
oval gear meter:
•
see chapter