417101438_EMPII_E60.docx
- 134 -
Rev. 11-02.14
14.1.3 Pump key definition
1. Electrical version
E 60
● On/Off switch for switching the pump
● mechanical stroke adjustment
● backlit graphical display, 4 control keys
● individual stroke control (each stroke is executed completely)
● metering control via stroke signal output (computed)
or via external metering monitoring system
● collection of operating and consumption data (computed)
● calibration function
configurable operation modes:
Internal operation
Setting of metering quantity/metering frequency in:
● Strokes/min.
● Percentage
● Litres/hr (or gallons/hr)
External operation
● Pulse operation (control via pulses)
-
Pulse multiplication (1 incoming pulse = n metering strokes)
-
Pulse division (n incoming pulses = 1 metering stroke)
● Standard signal operation (control via external standard signal 0/4 - 20 mA or 20 - 0/4 mA)
● Batch operation (a preset quantity is metered after being triggered by external enable pulse)
Inputs:
● low-level monitoring of bundle holder (reserve and empty report)
● pulse
● standard signal
● enabling signal (metering lock)
● metering monitoring
Outputs:
● low-level monitoring of bundle holder / fault (reserve and empty report)
● Fault report
● stroke signal
E 60
PLUS
●
similar to
E 60
, but with the addition of a
dongle box
for connecting of oval gear meter
OGM
PLUS
(expansion unit for the capture of operating data)
● display of the currently measured metering quantity and automatic readjustment of pump output
(only in conjunction with an external through flow monitoring system,
e.g. oval gear meter
OGM
PLUS
)
● automatic calibration function via oval gear meter
● consumption data monitoring via oval gear meter