background image

6.0  SYSTeM aDJUSTMeNTS

DETERGENT CONTROLLER P.C. BOARD

Figure 6-1

6.1  cell/Sensor Selection

Ensure jumper JP2 on the detergent controller PC board is 

set properly for the corresponding cell/sensor. For S-2000 

sensor operation, the jumper should only be installed on 

ONE pin of JP2.
For two-pole probe operation, the jumper should be installed 

on the right two pins of JP2, labeled "S26".

6.2  concentration adjustment

Concentration versus Conductivity

when the detergent is dissolved in the wash tank, it produces 

a certain 

concentration 

of product. A given concentration 

of product will, in turn, produce a corresponding 

conductiv-

ity 

signal that can be measured by the cell/sensor used by 

the detergent controller. The controller attempts to reach 

a desired solution concentration by using the conductivity 

signal to control when to feed detergent product into the 

wash tank.

However, the actual conductivity signal measured in the wash 

tank can vary significantly due to natural conductivity in the 

wash tank water. The detergent controller cannot distinguish 

between the conductivity signal produced by the water and 

that produced by the dissolved detergent.
For this reason, the setting of the TITRATION DIP switch 

should be viewed as a starting point that may require adjust-

ing once the wash tank is titrated.

Titration Adjustment

Adjustment of the wash tank concentration is done using 

the six position TITRATION DIP switch on the detergent 

controller PC board. The individual positions on this DIP 

switch are labeled 1 through 6. Sliding a position to the left 

will turn that position ON. Sliding a position to the right will 

turn that position OFF. when a position is ON, the detergent 

controller will add detergent to the wash tank according to 

the following table:
SWITCH 

 

POSITION ON 

6

APPROX. # 

GeO DROPS 

16 

32  64

APPROX. # 

STANDARD DROPS  1 

16  32

when multiple positions are ON, the detergent controller 

will add all positions together to achieve the desired tank 

concentration.

Example using Standard Drops: 

1.  Assume a desired tank concentration of 14 standard 

drops is required. Start by turning positions 

1

 and 

2

 and 

3

 

ON

. (2 + 4 + 8 equals 14)

2.  Allow the detergent controller to feed until the 100% 

LeD begins flashing rapidly. Immediately titrate the tank 

TITRATION ADJuSTMENT

SONALERT

®

 ALARM DE-

LAY ADJuSTMENT

SONALERT

®

 

ALARM VOLuME 

ADJuSTMENT

CeLL/SeNSOR

SELECTION

FEED ADJuST PO-

TENTIOMETERS

Note: JP1 and JP2 

jumpers in "open" 

position.

solution.

3.  If the actual titration measurement is only 10 drops, the 

wash tank water conductivity is already adding a read-

ing of 4 drops to the measurement. The TITRATION 

DIP switch must be readjusted to a setting of 18 to add 

additional detergent to the tank.

4.  Turn positions 

2

 and 

3

 OFF and position 

4

 ON. This 

results in positions 

1

 and 

4

 ON. (2 + 16 equals 18)

5.  Repeat  step  2. This  should  now  provide  the  desired 

concentration.

6.3  feed adjustment potentiometers

When the wash tank concentration is between 80% to 100% 

of the set point, the dispenser will provide an “on-off” pulse 

feed mode to control overshoot.
These potentiometers determine the duration of the “on-off” 

pulses. This allows for minimum overshoot dependent upon 

the detergent dispensing rate,

 refer to Figure 6-1.

The normal setting (as factory set) is both pots being in the 

full counter-clockwise position, providing for a 1 second “on” 

pulse and a 1 second “off” pulse. This is desirable for most 

operating conditions.
These are adjustable up to a maximum of 12 seconds. If 

the detergent delivery rate is very slow, such as might be 

encountered with low feed water temperature to the reservoir, 

it may be desirable to increase the “on” pulse time.
In a very large wash tank, it may be desirable to increase 

the “off” to allow the detergent to disperse evenly throughout 

the wash tank before further feeding occur.

Summary of Contents for GEOCENTER

Page 1: ...GEOCENTER Installation and Operation Manual Dispenser Complete 9223 1091 26392 0406 0409 Copyright Ecolab Inc 2009 9223 2610...

Page 2: ...This page intended to be blank...

Page 3: ...lation 5 4 6 VANGUARD Wash Max Installation 5 4 7 Geosystem Rinse Dispenser 6 4 8 Rinse Injector Connections 6 4 9 Hydraulic Connections and Visual Flow Indicator 6 5 0 ELECTRICAL CONNECTIONS 7 5 1 Tr...

Page 4: ...13 9 3 Unit does not feed Power Light on Feed Light not on 14 9 4 Feeds continuously Feed Light not on 14 9 5 Feeds continuously Feed Light on 14 9 6 Fluctuating titration 15 9 7 Excessive detergent c...

Page 5: ...ines will be suggested in reference to the preferred method of installation however the variety of equipment and the surrounding physical environment will dictate the actual installation of the GeoCen...

Page 6: ...ergent when wash tank concentration is near the desired control point Visual indicators signal concentration status of the wash tank A FEED light will illuminate when concentration is below the set le...

Page 7: ...a 440 volt installation IMPORTANT Make sure the power source is turned off 3 1 Dimensions Height H 7 5 8 19 4 cm Width W 11 3 8 28 9 cm Depth D 6 3 8 16 2 cm Weight 12 LB 5 4 kg 3 2 Access Requiremen...

Page 8: ...inimum 14 GA 600 volt insulated wire Wiring from the power source to the transformer must be enclosed in conduit seal tite or other housing approved for damp locations 3 5 Plumbing Requirements Water...

Page 9: ...er to Figure 4 1 Attach to plastic GeoCenter enclosure with 8 32 x 5 16 screw in kit bag Ground using green yellow wire 4 3 Mounting the GeoCenter 1 Mount the GeoCenter cabinet to the wall using the s...

Page 10: ...ID PVC tubing provided 3 Insert this injection tubing assembly fully into the outlet end of the Flow Indicator tube also called the sight tube 4 Secure all connections with the clamps provided 5 Comp...

Page 11: ...SOLID RINSE RESERVOIR RED BLACK GREEN WHITE HI S26 ON 10 11 12 13 14 15 16 17 18 19 20 21 22 23 OFF FEED ALARM VOLUME ALARM DELAY TITRATION ALARM 100 POWER LED LED JP2 FEED OFF FEED ADJUST 5 0 ELECTR...

Page 12: ...ductor cable between the GeoCenter and Detergent units At the GeoCenter Refer to Figure 5 1 on page 7 Wire nut the leads from the 2 conductor cable to the two WHITE wires provided with the wire nuts 5...

Page 13: ...8 16 32 64 APPROX STANDARD DROPS 1 2 4 8 16 32 When multiple positions are ON the detergent controller will add all positions together to achieve the desired tank concentration Example using Standard...

Page 14: ...ntrol the injection rate of the rinse additive can be controlled throughout the entire rinse cycle refer to Figure 6 2 Injection rate can also be adjusted by use of alternate sized squeeze tubes INJEC...

Page 15: ...limitations in sensor technology the thermistor in the S 2000 sensor responds slowly to changes in wash tank temperature Under certain conditions this slow response can cause the detergent controller...

Page 16: ...away from pump body until tubes slips over the rollers 4 Clean inside of pump body wiping to remove particle matter and accumulation of old lubricant 5 Inspect the roller assembly closely for signs o...

Page 17: ...at valve coil if present a Check for water to the valve b Disconnect the outlet tubing from the valve If water flowsthruthevalve checkforplugorrestrictionintubing to the reservoir or in the reservoir...

Page 18: ...lly increasing If not there is no detergent being delivered to the machine or the detergent is not feeding into the wash tank Check for proper water flow to the dispenser properoperationofthedispenser...

Page 19: ...wn wire from terminal 15 and readjust the titration according to section 7 4 If titrations stabilize use this setting for operation 3 Check for signs of moisture contamination on the de tergent contro...

Page 20: ...air leaks 2 Check for high rinse pressure optimum is 15 20 psig 1 1 4 BAR and cannot be over 35 psig 2 4 BAR 3 Check squeeze tube for wear and cracks etc 1 Lubricate use only silicon grease lubricate...

Page 21: ...ER W CELL PKD INJECTOR CONTROL BOARD 9217 0042 1 4 TO 1 8 REDUCING TUBE 1 5 9218 0884 SQUEEZE TUBE 1 4 cc 9217 0125 SQUEEZE TUBE 1 8 cc standard 9218 0892 SQUEEZE TUBE 1 2 cc 9218 0900 SQUEEZE TUBE 1...

Page 22: ...nse injector On these machines a constant power source L1 L2 is applied to the injector transformer and a rinse pressure switch will have to be installed The rinse injector will then be activated when...

Reviews: