6" MIN (uS)
30 cm (INT'L)
w
AT
ER FLOw
H
D
W
3.0 SpecIfIcaTIONS
System Diagram
An injection fitting assembly requires a 1/8 NPT tap into the
final rinse line.
3.4 electrical requirements
The GeoCenter operates on a 24 volt AC, 50/60Hz power
source supplied through two 30 VA transformers. The
transformer primaries can be either 115 or 230 volts. One
transformer provides power for the detergent control and
the other provides power for the rinse injector.
If the primary voltage is 440 volts, two separate, externally
mounted transformers will be required. The 24 volt secondary
wiring of one transformer will be connected directly to the
Detergent Controller P.C. Board. The 24 volt secondary of the
second transformer will be connected directly to the Rinse
Speed Control P.C. Board. Both the internal transformers
can be removed when wiring for a 440 volt installation.
IMPORTANT: Make sure the power source is turned off
3.1 Dimensions
• Height (H): 7-5/8" (19.4 cm)
• Width (W): 11-3/8" (28.9 cm)
• Depth (D): 6-3/8" (16.2 cm)
• Weight: 12 LB. (5.4 kg)
3.2 access requirements
Mounting location must allow cabinet cover to swing down
180° for adequate installation and service. Allow room on
the right side to service the peristaltic pump, and on the left
for electrical service.
3.3 product pickup and Discharge
The pick-up tubing, 1/8" (3.2 mm) Polyflo, must not
exceed 10' (3 meters) in length. The maximum discharge
tubing length of 150' (45 meters) will accommodate
remote installations of the GeoCenter. If tubing length
exceeds 50' (15 meters) the tubing must be replaced with
1/4" (6.3 mm) Polyflo tubing to minimize back pressure.
SOLENOID VALVE
(REFER TO FIGuRE 4-4 ON
PAGE 6.)
DETERGENT CONTROLLER
P.C. BOARD
RINSE SPEED
CONTROL P.C. BOARD
TRANSFORMER ASSEMBLY
(REFER TO FIGuRE 5-2 ON
PAGe 8.)
INJECTION POINT
TO GEOSYSTEM
RINSE DISPENSER
WASHTANK
S-2000
SENSOR
VACUUM BReAKeR
VISuAL FLOw INDICATOR
CHeCK VALVe