EcoFoot5D Install Guide V1.1-FINAL
Page 11 of 19
January 25, 2018, ES10560
ecolibriumsolar.com
Appendix A: Grounding & Bonding
The EcoFoot5D system has been tested by TüV Rheinland and conforms to UL 2703 for Grounding and
Bonding when installed per the published installation instructions.
EcoFoot5D carries module-to-module ground bond through the Wind Deflector and Mid-Support – Items 5 and
Items 7 & 8 respectively, listed in the “EcoFoot5D Core Components” table in this document.
Each row of modules/wind deflectors in an array of up to 400 modules must be grounded per the NEC and
ANSI/NFPA 70 either through the designated ground hole in the Wind Deflector, or by drilling a ¼” ground hole
into the Wind Deflector a minimum of ½” from any edge. One Ground Lug is required for every 400 modules
connected within an array.
Ecolibrium Solar recommends using #6 copper ground wire in conjunction with WEEB grounding devices such
as the WEEB-LUG-6.7 or WEEB DSK516. Lugs are a single use component.
Other grounding methods must be reviewed and approved by a licensed master electrician or electrical
engineer and Authority Having Jurisdiction (AHJ).
Green lines represent ground bond path.
Wind Deflectors carry module-to-module
east/west ground bond. Mid-Supports carry
row-to-row north/south ground bond.
Grounding and Bonding Path
Ground Lug
Ground Hole with Lug Installed
Ground Lug is installed in the Wind Deflector
either in the designated ground hole or by
drilling a ¼” ground hole into the Wind
Deflector a minimum of ½” from any edge.
One Ground Lug is required for every 400
modules within an array.
Ground Lug
▲