11 | ZincBlue2 User Manual
Physical Characteristics
ZincBlue2 Battery Panel 500W
.................1.1"H x 19"W x 24.4"D 24.4 lbs.
ZincBlue2 Battery Module 500W
..............2.3"H x 17"W (19” w/ mounting) x 12.1"D 21.1lbs.
ZIncBlue2 XRT Battery Introduction
The Econolite ZincBlue2 XRT Battery 3600Wh (ZincBlue2 XRT) is available in one form factor and comes with the
ZincBlue2 XRT Battery 3600Wh IMS and four monobloc nickel-zinc batteries.
ZincBlue2 XRT comes with a 3600Wh intelligent management system that connects to four 1kW monobloc
nickel-zinc batteries. For full operation, the system must include the ZincBlue2 UPS and PIM.
ZincBlue2 XRT Overview
1. COLD START/FORCE OFF
Manually cold start the ZincBlue2 XRT to enable quick startup of an intersection. With the monobloc nickel-zinc
batteries connected, push and hold for 5-8 seconds for immediate system cold startup. Hold for 10-20 seconds to
turn off.
2. BATTERY OUTPUT
The connection point between the ZincBlue2 XRT and ZincBlue2 UPS 1000W/1500W via the provided Digital and
DC Power Interconnect Cable.
3. AC INPUT
The connection point between the ZincBlue2 XRT and PIM via the provided Locking AC Power Interconnect Cable.
Note: If installing multiple ZincBlue2 XRT Battery 3600Wh units, each additional unit will need to be
independently connected to a 20Amp protected AC circuit via the AC INPUT port on the front of the ZincBlue2
XRT Battery 3600Wh IMS with the XRT AC Power Cable. Additional ZincBlue2 XRT Battery 3600Wh units cannot
be daisy-chain connected to the PIM.
1 6 8
2
3
7
9
4
5
ZincBlue2 XRT Battery 3600Wh IMS
Z5 13-80 H S F
1kW Monobloc Nickel-Zinc Battery