ZincBlue2 User Manual | 80
ZincBlue2 PIM
The PIM is the device that routes all the power in the system. It takes AC Power from the Utility and re-routes it
through the AUTO BYPASS RELAY and 15Amp breaker (UPS TEST SWITCH) to the ZincBlue2 UPS 1000W. The PIM
directly, without breaker, routes AC to the Battery Panel/Battery Module (BATTERY AC OUT). The ZincBlue2 UPS
1000W/1500W returns AC Power back to the PIM (FROM UPS AC OUT) and routes this through a 20Amp circuit breaker
and AUTO BYPASS RELAY to the cabinet load. Terminal blocks for INPUT (from Utility) and OUTPUT (To Cabinet) are iso-
lated via conduit input hole and cover. The terminal blocks can accept 10-12 AWG wire using a ring terminal or spade
terminal.
The UPS TEST switch on the PIM can be utilized to test the ZincBlue2 UPS 1000W/1500W which will go into backup
mode by turning the switch from ON (UPS Mode) to OFF (TEST Mode). Because Utility power goes directly to the Bat-
teries (TO BATTERY AC IN) the UPS TEST switch should not be used for run-time testing. The UPS TEST OUTPUT can be
used at any time to monitor AC Voltage coming from the ZincBlue2 UPS 1000W/1500W.
The BYPASS light will go ON anytime there is no ZincBlue2 UPS 1000W/1500W in the system (unplugged, damaged,
etc.) The Auto BYPASS relay will route the incoming UTILITY INPUT directly to the CABINET LOAD output.
ZincBlue2 PIM Block Diagram