ZincBlue2 User Manual | 82
Troubleshooting
Trouble Analysis
Checking Process:
1)
Check system to make sure everything is working properly:
a.) PIM BYPASS (RED) light should be OFF: Power is going through ZincBlue2 UPS 1000W/1500W.
b.) Battery Panel/Module LED should be: Blinking White (monitor), or Blue (Charge) or Green (Discharge).
c.) ZincBlue2 UPS 1000W/1500W should not have any RED LIGHTS or warning notifications.
2)
Check all AC (Power) connections from the PIM to the other devices. Confirm nothing is loose.
3)
Check that Battery Interconnect Cables between batteries and ZincBlue2 UPS 1000W/1500W are all secure
and attached.
Test:
The UPS TEST switch can be utilized as needed to verify the ZincBlue2 UPS 1000W1500W is working properly.
1)
Place the UPS TEST switch in the OFF position to remove utility input power going to the ZincBlue2 UPS
1000W/1500W. This will force the system into backup mode. The ZincBlue2 UPS 1000W/1500W will then
provide power to the CABINET LOAD and the UPS TEST OUTPUT on the PIM.
2)
Confirm the ZincBlue2 UPS 1000W/1500W is in BACKUP MODE:
a.) ZincBlue2 UPS 1000W/1500W has BACKUP MODE ON – Solid Green LED.
b.) The Battery Panel/Module LED – Solid Green LED.
3)
If a RUN TIME test is desired it is best to leave the UPS TEST switch in the ON position and turn off the
utility power off at the breaker going to the PIM. This will force the ZincBlue2 UPS 1000W/1500W into
backup mode and keep the batteries from being charged.
Troubleshooting Sequence Chart
The Troubleshooting Sequence Chart applies to both the ZincBlue2 UPS 1000W and 1500W.
Start
1) Check all AC cables attached
2) Confirm UPS TEST switch is in ON position
3) Confirm AC is wired to PIM Utility Input, powered
ON and Hot and Neutral are not reversed.
ZincBlue2 UPS 1000W
not powering on?
1) Check cabinet wiring on PIM (Hot, Neutral, and
Ground). Rewire as needed.
2) Check that batteries are charged and attached.
3) Confirm input voltage is within specification.
4) Confirm output load does not exceed 1000W
5) If TIP switch is enabled make sure device is level.
6) Confirm output circuit breaker not open.
Yes
ZincBlue2 UPS
1000W
is ON but
Red Light is ON or
Blinking?
No
Yes
ZincBlue2 UPS
1000W
goes into
battery backup
mode too easily
No
1) Disable Enhanced sensitivity mode.
2) Adjust the Power Fail Threshold ranges.
3) Verify the cabinet wiring, especially Neutral.
Yes
BYPASS MODE LED is
always RED.
1)
Check AC Power from UPS to PIM
2)
Confirm output circuit breaker is
closed.
3)
Confirm
ZincBlue2 UPS 1000W
is
ON (LCD is ON)
Yes
No
End
No
ZincBlue2 Troubleshooting Flowchart