background image

83  |  ZincBlue2 User Manual

Problem

Solution

The ZincBlue2 UPS 1000W/1500W not getting AC Power

1) Check AC TO UPS cable from PIM is attached and supplying 120Vac.
2) Confirm UPS TEST switch on PIM is in the ON position.

The ZIncBlue2 UPS 1500W cold start is not working

With no AC power the system can be started from the battery cold start button. The ZincBlue2 UPS 1500W will enforce the minimum battery configuration: two 
500W panels or modules orUPStealth 2 XRT Battery 3600W must be attached. If only one 500W panel/module is attached to the ZincBlue2 UPS 1500W a cold 
start will not work.

Utility AC is applied with a cabinet miswire of swapped Hot and Neutral. Check the cabinet wiring to the PIM (Hot, Neutral, Ground) terminal block and rewire as necessary.

Enhanced Sensitivity is Enabled

Turn off Enhanced Sensitivity. This mode increase the ZincBlue2 UPS 1000W/1500W sensitivity to power failures and glitches and when it will switch from AC line 
power to backup mode.

Power Fail Thresholds range is too restricted

Change the LOW and HIGH Threshold to specify when the ZincBlue2 UPS 1000W/1500W should go into battery backup mode. A wider range will reduce 
sensitivity.

Poor cabinet neutral

Verify cabinet wiring.

Intermittent power connections from utility

Verify cabinet wiring--check for loose wires.

Adjust the Line Qualify Time

By default the line qualify time is set to 30s. After power is restored the system will remain in backup for the Line Qualify time. This can be adjusted from 30s to 
10s or 3s.

Batteries not attached or available

1) Check battery interconnect cable is connected between ZincBlue2 UPS 1000W/1500W and each battery. Confirm that when plugged in the UPStealth 2 UPS 
1000W/1500W recognizes the batteries (a dot on the LCD will light up for each battery detected).
2) Confirm the batteries are also connected to the PIM via AC cable.
3) The 1500W requires a minimum of one ZincBlue2 XRT Battery 3600W or two 500W ZincBlue2 Battery modules/panels. Confirm the system meets this 
requirement. If the minimum configuration is not met, then the LCD will display: STATUS: BACKUP UNAVAILABLE

Batteries voltage is too low (not charged)

Batteries will blink the LED White when fully charged. If system has recently been through a discharge cycle the batteries may not be charged up sufficiently to 
provide backup power (voltage will be too low).

The UPS input voltage is out of spec

Check incoming AC voltage is present and within spec: 85-140Vac.

The UPS inverter is not operational

Contact technical support.

The load is too high for the UPS
(Inverter Overload)

Confirm the total load on the PIM connected to UPS TEST OUTPUT and CABINET LOAD does not exceed the 1000W max rating of the ZincBlue2 UPS 
1000W/1500W.

The temperature is outside the operational range of the UPS

Check system is within its operational temperature range: -37C to 74C.

The tip switch is activated while the UPS is in backup mode.

Device is out of level by > 15 degrees. Return to a level state. Power cycle the ZincBlue2 UPS 1000W/1500W  as needed to clear fault.

Status screen states BACKUP UNAVAILABLE

This status will be present if the AC Power and UPS Output are out of specification (too high > 124V or too low < 116V). Also, an excessive loads on inverter can 
cause this.

Output Circuit Breaker maybe Open

The output circuit breaker is a 20Amp push button breaker. Make sure the white button is pressed in all the way (flush to the plastic). Confirm voltage at Cabinet 
load reads 120Vac.

A single Beep is heard.

This is normal and represents:
System going from NORMAL to BACKUP mode
System going from BACKUP to NORMAL mode

Emits single beep and has RED LED on the UPS

The load is too high for the UPS (see "UPS 1000 cannot provide battery backup")

ZincBlue2 UPS 1000W/1500W emits a long beep, followed by a string of 6 
short beeps

The inverter cannot detect batteries.  Confirm all battery connectors are fully seated.
Make sure battery LEDs are all on.

Batteries are not completely charged or are near the end of their service 
life.

1) Make sure batteries are fully charged (White light blinking) and not in charge mode (Blue light) when doing run time testing.
2) Hot and cold extreme temperatures can impact runtime.  Perform a run time test between 20C - 40C for best comparison testing.

Cabinet may have poor power factor.

Account for power factor as part of the load.

The batteries are not being charged.

The battery panels and modules will only charge between -37C to 50C, outside of this temperature range, as measured by the internal battery temperature 
sensors, the batteries will not attempt to charge. 

The ZincBlue2 UPS 1500W inverter not working with 1 battery 
panel/module

The ZincBlue2 UPS 1500W requires two 500W UPStealth 2 Battery Panels or Modules or UPStealth 2 XRT Battery 3600Wh in order to work properly (allow 
discharge). If it doesn't meet this requirement an error will be noted.

The ZincBlue2 UPS 1500W inverter is making clicking noises

The ZincBlue2 UPS 1500W is going through initialization and startup of the inverter. If this continues check battery connection; batteries maybe missing.

An invalid Subnet Mask was entered making it impossible to connect with 
UPS 1000.

If an invalid Subnet Mask was entered it will require doing a "Config Data Only" reset from the LCD:  STATUS > SETTINGS > ADDITIONAL SETTINGS > SYSTEM 
RESETS page.

System shows Backup unavailable and writes Inverter out of Spec 
Warning in the System Log

The 1500W controller output voltage is either less than 100V or greater than 130V. This device will not be able to go into backup when power is removed. 
Problem is likely a damaged or locked out inverter.  Check to make sure the output load (<=1500W) and battery voltages (43-60VDC) supplying the unit are 
within range.

System writes Inverter out of Spec Warning in the System Log.

The 1500W controller output voltage is either less than 115V or greater than 124V. The BACKUP mode will still be operational. A high output load and/or low DC 
(battery) voltage can contribute to the inverter going slightly out of spec. Confirm load is <=1500W.

The LED on the Battery Panel/Module is RED

This can occur if there is a hardware failure or if the cold start button is pressed for over 10 seconds while the  battery is powered by AC. 
 
Remove AC from the Battery Panel/Module.  Force battery off by holding COLD START button down for 10S to turn RED LED OFF.  Return AC power and perform 
a Power Loss test to confirm battery will go into backup mode (GREEN LED). If RED light remains on the battery panel/module contact technical support.

The LED on the Battery Panel/Module is ORANGE

Indicates a HW failure. Contact ZincFive technical support.

Always in BYPASS mode (BYPASS LIGHT IS RED)

1) System will go into BYPASS mode when the ZIncBlue2 UPS 1000W is not connected to the PIM or not operational. Make sure the AC power from the PIM is 
connected to the UPS 1000W; both input and output AC must be connected. Confirm UPStealth 2 UPS 1000W/1500W is active (LCD is ON).
2) Internal contactor maybe damaged.

Device not powering up

1) Check to make sure AC and DC breakers are in ON position (switch flat).
2) Confirm AC plugged in.
3) Confirm all battery cables attached to XRT and wired to their respective battery
4) Confirm the External Temperature Sensor is attached to battery lug and plugged in.

All four battery status LEDs are blinking red

This is a Hardware fault. Likely issues is the Temperature Sensor is not plugged in / missing or damaged. 
Note: The XRT system will shut down during backup or prevent the XRT from going into backup if the temperature sensor is missing.

All four battery status LEDs are solid red

This will occur when one or more of the batteries are unplugged or miswired. Check to make sure the battery cable is connected and properly wired to the 
battery (Red wire to positive terminal and Black wire to negative terminal). Check the fuse in each of the battery cables to make sure that none have opened.

XRT is not charging the batteries

The LN3 batteries will only be charged between -25C to 50C, outside of this temperature range, as measured by the external temperature sensor, the batteries 
will not attempt to charge. The system has a 5C hysteresis before returning to charging after exceeding the temperature limits.

XRT is not discharging the batteries at extreme temperatures

There is a low and high temperature limit on discharge. The Batteries will NOT discharge once the external temperature sensor attached to the battery terminal 
is less than -37C or greater than 74C.  This is to preserve the life of the battery and system.

Battery cable removed during operation

Removal of any individual battery cable during backup mode will cause the XRT / UPS to power down. Removal during charge or monitor mode will cause all four 
battery status LEDs  to be sold red notifying the user of an error.

One battery status LED is blinking red 

This indicates a weak or bad battery conditions.
The ZincBlue2 UPS 1000W/1500W will notify the user via Battery Attention warning. The red status LED will begin blinking for the corresponding bad battery. 
The blinking RED status LED will be cleared once the battery is removed and replaced.

Firmware update failure

Make sure there is nothing plugged into the micro-USB connector. Note: The micro-USB port is for factory/field service use only.

Battery Attention seen in the system log

The three conditions that will trigger a battery attention log are:
1) Temperature Sensor Failure, 2) Weak or bad battery detected, 3) Power supply failed to respond.
Power should be recycled on unit and connections (including battery fuses) should be re-checked.

ZincBlue2 XRT Battery 3600Wh 

ZincBlue2 UPS 1000W/1500W not powering ON

ZincBlue2 UPS 1000W/1500W RED LED Flashing

ZIncBlue2 UPS 1000W/1500W is too sensitive in going into battery backup mode

ZincBlue2 UPS 1000W/1500W stays in backup mode too long after power is restored

ZincBlue2 UPS 1000W/1500W cannot provide battery backup (UPS FAULT: Red LED ON)

The ZincBlue2 UPS 1000W/1500W emits an audible beep

The ZincBlue2 system does not meet expected backup time

The ZincBlue2 other

Battery Fault

Power Interface Module (PIM)

ZincBlue2 Troubleshooting Chart

Summary of Contents for ZincBlue2 UPS 1000W

Page 1: ...ZincBlue2 Manual...

Page 2: ...This user manual provides the essential information you need in order to get the most from your ZincBlue2 Uninterruptible Power Supply ZincBlue2 Software Copyright 2021 Econolite All rights reserved...

Page 3: ...31 Sch ma de c blage d ZincBlue2 32 Wiring the ZincBlue2 XRT 32 Connecting ZincBlue2 XRT to UPS and PIM 32 Installing Additional ZincBlue2 XRT Battery 3600Wh 33 ZincBlue2 XRT Wiring Diagram ZincBlue2...

Page 4: ...limentation en courant continu 29 C ble d interconnexion num rique et d alimentation en courant continu 29 Verrouillage du c ble d interconnexion d alimentation en courant alternatif 29 C ble d alimen...

Page 5: ...orks of the manufacturer Trademarks ZincBlue is a registered trademark of Econolite Use of third party trademarks brand names trade names and or prod uct names are for informational purpose only and a...

Page 6: ...t www econolite com support or call 800 225 6480 ZincBlue2 Recycling Econolite cares about our environment and has made arrangements for users to easily recycle all ZincBlue2 components including the...

Page 7: ...f liquid enter the UPS and batteries Do not operate the UPS and batteries with damaged cables and wires Defective cables and wires must be replaced before system installation Prior to system installat...

Page 8: ...done or supervised by personnel knowledgeable about batteries and the required precautions Battery Panel Module must not be installed in a sealed enclosure ventilation must be provided Use proper lif...

Page 9: ...s endommag s Les c bles et fils d fectueux doivent tre remplac s avant l installation du syst me Avant l installation du syst me v rifier que tous les c bles et fils sont correctement fix s et connect...

Page 10: ...ge 120Vac Nominal 85 140Vac User Programable Input Current 15A max Input Frequency 60Hz nominal 10 54 66Hz Output Voltage 120Vac 3 Output Current 8 3A Typical Output Power 1 000VA Typical Output Frequ...

Page 11: ...s pre event and 250ms post event sine cycles along with a day date time stamp in the event log Up to 1000 events with waveforms can be stored in the event log and accessed through the browser based Zi...

Page 12: ...SAVE funtion 7 NAVIGATION DIAL Rotating navigation dial for control of the LCD screen cursor Pushing the dial functions as a Select button 8 BATTERY INPUTS Six 6 battery inputs for connecting battery...

Page 13: ...een the Battery and PIM Use the provided Locking AC Power Interconnect Cable 4 HANDLE Used for lifting the battery panel 5 STATUS A multi color LED indicators that provides battery status Green Backup...

Page 14: ...tartup of an intersection With the monobloc nickel zinc batteries connected push and hold for 5 8 seconds for immediate system cold startup Hold for 10 20 seconds to turn off 2 BATTERY OUTPUT The conn...

Page 15: ...charge mode Red Green Alternating Weak battery detected discharge mode 6 MICRO USB PORT Reserved for manufacturer use 7 AC POWER A 20Amp Breaker to turn AC ON OFF 8 BATTERY TEMPERATURE Battery Tempera...

Page 16: ...un module de batterie connect l ASC appuyer et maintenir pendant 5 secondes pour un d marrage froid imm diat du syst me Maintenir pendant 10 secondes pour l teindre 2 SORTIE DE LA BATTERIE Le point de...

Page 17: ...onnecter le c ble CA la nouvelle batterie Le d branchement des piles puis es avant de brancher des piles neuves peut entra ner l arr t pr matur du syst me lorsqu il est en mode de d charge Lorsque le...

Page 18: ...OAD 20A breaker protection for the load 7 UPS TEST 15A breaker switch on incoming utility AC power In the ON position the AC from utility input is connected to the ZincBlue2 UPS 1000W 1500W providing...

Page 19: ...packaging The ZincBlue2 system should be installed in a restricted access environment and only installed and serviced by authorized personnel Tools Needed Slotted screwdriver 1 8 and 3 16 1 8 used for...

Page 20: ...e on Disconnect the ZincBlue2 UPS 1000W 1500W from AC Power and adjust the rack or shelf mounting so that the device does not tilt in excess of 15 degrees from level Then connect AC Power back to the...

Page 21: ...own in the below figures The space bar and speedy sleeve will assist with installation use the provided figures and steps to install the ZincBlue2 Battery Panel Step 1 Spacer Bar Insert the spacer bar...

Page 22: ...placed on a shelf For shelf installations no other hardware is needed For rack installation use the provided bracket 1 and screws 4 as shown in the figure below Battery Module Rack Mount Installation...

Page 23: ...st me ZincBlue2 doit tre install dans un environnement acc s restreint et ne doit tre install et entretenu que par du personnel autoris Outils requis Tournevis fente 1 8 po et 3 16 po 1 8 po utilis po...

Page 24: ...e ZincBlue2 500 W Le module de batterie ZincBlue2 est install par montage en tag re ou en rack Pour une installation d tag re aucun autre mat riel n est n cessaire Pour l installation en rack utiliser...

Page 25: ...terconnect Cable to allow wall outlet charging of Battery Panel and Module QTY 1 Length 48 to 6 10 split Cable used to daisy chain AC Power between batteries QTY 1 Length 6ft Cable used to interconnec...

Page 26: ...erly attached to the wires The correct torque for the terminals is 16 in lbs Note A Listed Type 1 or Type 2 Surge Protective Device having a VPR rating maximum 1500 Vpk transient voltage shall be prov...

Page 27: ...connection are CLASS 2 H G F E D C B A 8 7 6 5 4 3 2 1 H G F E D C B A 8 7 6 5 4 3 2 1 H G F E D C B A 8 7 6 5 4 3 2 1 H G F E D C B A 8 7 6 5 4 3 2 1 Common C Normally Open NO Normally Closed NC N No...

Page 28: ...the TO BATTERY AC IN on the PIM using the supplied Locking AC Power Interconnect Cable and AC Power Daisy Chain Cable as needed When the battery unit is connected to AC the battery unit LED should Wh...

Page 29: ...2 26 18 DW Class 2 Relay connections Class 2 Relay connections AC FROM UPS AC G ND AC AC G ND AC AC GND AC AC GND AC N G L G N L NEUTRAL BUSS EQ GND TO CABINET EQUIP MENT AC INPUT UTILITY POW ER INPUT...

Page 30: ...tilis pour toutes les interconnexions d alimentation en courant alternatif entre l ASC et le MIA et entre le MIA et la batterie QT 1 Longueur 1 pi Adaptateur pour le verrouillage du c ble d interconne...

Page 31: ...n de la ligne d utilit au MIA ENTR E UTILITAIRE avec des fils de 10 12 AWG et des bornes anneaux de taille n 8 fix es aux fils Le couple correct pour les terminaux est de 16 in lb 4 Avec seulement l E...

Page 32: ...6 5 4 3 2 1 H G F E D C B A 8 7 6 5 4 3 2 1 H G F E D C B A 8 7 6 5 4 3 2 1 H G F E D C B A 8 7 6 5 4 3 2 1 Common C Normally Open NO Normally Closed NC R Re em ma ar rq qu ue e Les contacts secs sont...

Page 33: ...dre le syst me 2 Connecter l entr e CA du panneau de batterie ou du module de batterie de l ZincBlue2 l entr e CA DE LA BAT TERIE sur le MIA l aide du c ble d interconnexion d alimentation CA verrouil...

Page 34: ...tions Class 2 Relay connections AC FROM UPS AC G ND AC AC G ND AC AC GN D AC AC GN D AC N G L G N L NEUTRAL BUSS EQ GND TO CABINET EQUIP MENT AC INPUT UTILITY POW ER INPUT G N ZincBlue2 UPS 1000W Fron...

Page 35: ...ER breakers on the ZincBlue2 XRT 2 Connect the ZincBlue2 XRT BATTERY OUTPUT to the BATTERY INPUT of the ZincBlue2 UPS 1000W 1500W via the provided Digital and DC Power Interconnect Cable Note If the C...

Page 36: ...MS FRONT VIEW EXT TEMPERATURE SENSOR ZincBlue2 UPS 1000W 1500W FRONT VIEW ZincBlue2 UPS 1000W 1500W REAR VIEW PIM AC GND AC GND AC AC L G N 30A 30A CIRCUIT BREAKER MAINS TERMINAL BAR BONDED TO CABINET...

Page 37: ...supplying backup power and the batteries are below 10 capacity The green LED will flash at a frequency of twice per second RELAY TRIGGERED Solid Yellow The solid yellow LED will be ON any time one of...

Page 38: ...NOR MAL status CAPACITY Total remaining capacity of all attached batteries from 100 completely charged to 0 completely discharged BATTERY ATTACHMENT DIAGRAM A series of six circles to indicate the si...

Page 39: ...UPS 1000W 1500W switches from Utility power to Battery power the top line of the main status display will be STATUS BACKUP This indicates that the ZincBlue2 is using battery power Notes STATUS BACKUP...

Page 40: ...are numbered sequentially EVENT TYPE Shows the event that caused the log entry TIME STAMP Shows the date and time of the log entry For POWER RESUME logs the duration of elapsed time since the POWER FA...

Page 41: ...pty circle indicates that the relay is OFF A filled in circle to the right of a relay indicates that the relay is ON The relay status will continually be updated as long as the screen is visible Press...

Page 42: ...u to set the UPS date and time clock Also allows configuration of daylight saving time EVENTS Allows you to define edit or delete events Events are a collection of triggers and log events POWER FAIL T...

Page 43: ...time stamped with the system time and date On The Display SET TIME FORMAT Allows you to choose 12 hour or 24 hour time display SET TIME Allows you to set the current time DAYLIGHT SAVING TIME Allows y...

Page 44: ...me is displayed in 12 hour or 24 hour format On The Display 24 HOUR FORMAT Allows you to choose 24 hour time display Select this option with the Navigation Dial and then press the dial 12 HOUR FORMAT...

Page 45: ...Dial to select hours rotate the dial to increment or decrement the hours and then press the dial to set the hours value and select the minutes Rotate the dial to increment or decrement the minutes an...

Page 46: ...aylight saving time On The Display TURN ON DST The system clock will automatically adjust for daylight saving time Select this option with the Navigation Dial and then press the dial TURN OFF DST The...

Page 47: ...format On The Display MM DD YY FORMAT Allows you to display the date using the month day year format Select this option with the Navigation Dial and then press the dial YY MM DD FORMAT Allows you to...

Page 48: ...nt the day 01 31 and then press the dial to set the day value and select the year Rotate the dial to increment or decrement the year 00 99 and then press the dial to set the year value To Set the Date...

Page 49: ...not be triggered To program OR functions Set up an Event as shown in the section DEFINE EVENT and assign it a single trigger Then assign the Event to a Relay Repeat this process using an additional E...

Page 50: ...allows you to adjust the delay time after a power failure before the trigger is activated SYSTEM FAULT Enable the System Fault trigger TIME Allows you to configure the time of day trigger BATTERY CAPA...

Page 51: ...ine a delay time in hours after a power failure before this trigger becomes TRUE The delay time is set in increments of 0 5 hours to a maximum of 8 0 hours The default value if none is specified is 0...

Page 52: ...d by the ZincBlue2 Software On The Display Press the BACK button when you are finished configuring this trigger You will be taken back to the DEFINE EVENT screen where you can configure additional tri...

Page 53: ...me in 5 minute increments Use the Navigation Dial to highlight END rotate the dial to select the end time and then press the dial to set the value Press the BACK button when you are finished configuri...

Page 54: ...igger will be TRUE Use the Navigation Dial to highlight BATTERY CAPACITY rotate the dial to select the percentage and then press the dial to set the value Press the BACK button when you are finished c...

Page 55: ...ent created through the LCD interface on the ZincBlue2 You must use the ZincBlue2 Software to configure SMTP or SNMP notifications On The Display Use the Navigation Dial to highlight the relay to use...

Page 56: ...ssing the BACK button from the DEFINE EVENT screen the EVENT SAVE CONFIRMATION screen will prompt you to save your event On This Display The system creates an event name consisting of one or more of t...

Page 57: ...ET HIGH THRESHOLD Allows you to specify the maximum utility AC voltage threshold If utility voltage goes above this threshold the ZincBlue2 will switch to battery power ENHANCED SENSITIVITY When choos...

Page 58: ...1000W 1500W will switch to battery power On The Display LOW THRESHOLD Allows you to specify the minimum utility AC voltage before the ZincBlue2 will switch to battery power Rotate the Navigation Dial...

Page 59: ...1000W 1500W will switch to battery power On The Display HIGH THRESHOLD Allows you to specify the maximum utility AC voltage before the ZincBlue2 will switch to battery power Rotate the Navigation Dial...

Page 60: ...F Turn the Navigation Dial to turn ON or OFF enhanced sensitivity and then press the dial to set the value OFF sensitivity is selected by default Press the BACK button when you are finished configurin...

Page 61: ...cycling noisy power or power frequency mismatches after a utility power failure On The Display SECONDS Allows you to select the time period in seconds that the utility power must be within quality par...

Page 62: ...rent IP address The default IP address is 192 168 1 51 and may only be changed using the ZincBlue2 Software MAC ADDRESS Displays the MAC address of the ZincBlue2 This value is not user changeable Pres...

Page 63: ...n after selecting this option Press the Navigation Dial to confirm your request CONFIG AND FIRMWARE Resets the ZincBlue2 configuration data to factory default values reloads the originally installed f...

Page 64: ...ctory programmed to have the Tilt Switch disabled off which is displayed on the screen TILT ON Rotate the Navigational Dial left right to enable the Tilt Switch function Press the Navigational Dial to...

Page 65: ...splay the firmware version and whether the Tilt Switch function if avilable On The Display FW REVISION Displays the current firmware version TILT SWITCH AVAILABLE Displays on screen if enabled POWER R...

Page 66: ...attery charge status and runtimes View real time cabinet power consumption Configure Simple Network Management Protocol SNMP communication to be notified of system status Assign a name to a ZincBlue2...

Page 67: ...Click on Network and Internet Click on Ethernet Change Adapter Options Select an ethernet port right click and select Properties Find and select Internet Protocol Version 4 TCP IPv4 Click Properties...

Page 68: ...ogin screen When this screen appears enter your username and password and click the Login button IMPORTANT Each ZincBlue2 comes with the preset username admin and the preset password user System will...

Page 69: ...ens a page used to view captured events RELAY STATUS opens a summary page showing the 8 relays and whether they are triggered on or off EVENTS opens a page used to configure or edit events that you wa...

Page 70: ...that have taken place in the traffic cabinet For each event the main view lists the event s log number the event source a time stamp showing when the event occurred an error message the system ID and...

Page 71: ...of Specification AC Wiring Error Controller Temperature out of specification Inverter Locked out Excessive Load System Shutdown Battery Charger Firmware Updated System Config Change Time Format System...

Page 72: ...69 ZincBlue2 User Manual Relay Status Tab The Relay Status tab shows the status of the eight user programmable relays on the UPS indicating whether each is on or off Relay Status Tab...

Page 73: ...The tab displays a list of Events and clickable actions like Add Event and Delete Event buttons and No Event Configured Please Click here to add one To delete an existing event select that event in t...

Page 74: ...ect and remove triggers or add new ones 3 You will be asked to define an event outcome If there are no outcomes defined for the event there will be a button to click to add one If there are outcomes y...

Page 75: ...power signal must be within quality parameters before the system comes out of backup mode The options for this setting are 3 10 or 30 seconds If the UPS detects unacceptable AC power quality within th...

Page 76: ...users to log in to a specific ZincBlue2 Gateway Address Sets the IP address of the gateway that the ZincBlue2 will use Subnet Sets the subnet that the ZincBlue2 unit will be on DHCP enabled Check thi...

Page 77: ...le If you update your firmware but then introduce a new battery to the configuration you will need to update the battery firmware as well To update the Firmware and Software for ZincBlue2 visit the Ec...

Page 78: ...entries or in the ZincBlue2 application will be automatically adjusted to be consistent with the unit s local time The Enable Daylight Saving Time checkbox sets the ZincBlue2 unit to automatically ad...

Page 79: ...t password user To reset the password you will be asked to enter the old pass word and the new password then re enter the new password to confirm Passwords can be up to 32 characters long and contain...

Page 80: ...tbeat messages to indicate the system is still powered on and able to notify the SNMP server that it is able to communicate Event Destination Email Address Email address where event messages will be s...

Page 81: ...tage frequency and waveform anomalies When the pre defined or user defined AC thresholds are exceeded the ZincBlue2 UPS 1000W 1500W will transfer from AC Utility power to battery backup The ZincBlue2...

Page 82: ...discharge These devices communicate via CAN bus across the battery Digital and DC Power Interconnect Cable with the ZincBlue2 UPS 1000W 1500W Upon loss of power the ZincBlue2 UPS 1000W 1500W will sig...

Page 83: ...so lated via conduit input hole and cover The terminal blocks can accept 10 12 AWG wire using a ring terminal or spade terminal The UPS TEST switch on the PIM can be utilized to test the ZincBlue2 UPS...

Page 84: ...service or the battery temperature senor cable is unplugged The ZincBlue2 XRT uses several different modes which include Constant Current and Constant Voltage to optimize charging and balancing the b...

Page 85: ...ED 3 If a RUN TIME test is desired it is best to leave the UPS TEST switch in the ON position and turn off the utility power off at the breaker going to the PIM This will force the ZincBlue2 UPS 1000W...

Page 86: ...h initialization and startup of the inverter If this continues check battery connection batteries maybe missing An invalid Subnet Mask was entered making it impossible to connect with UPS 1000 If an i...

Page 87: ...are no warranties for loss of data No other warranties are expressed or implied 4 This Limited Warranty only applies to defects which may have arisen from system failures related to components or wor...

Page 88: ...tended warranty can be purchased at time of original purchase on a per year basis up to three additional 3 years 11 Written authorization for the warranty return of merchandise RMA must be obtained fr...

Page 89: ...ndth of a second NC Normally Closed Contact circuit completed NEMA National Electrical Manufacturers Association Nickel Zinc Rechargeable battery chemistry that uses Nickel and Zinc NiZn NO Normally O...

Page 90: ...87 ZincBlue2 User Manual Notes...

Page 91: ...This user manual provides the essential information you need in order to get the most from your ZincBlue2 Uninterruptible Power Supply ZincBlue2 Software Copyright 2021 Econolite All rights reserved...

Page 92: ...Econolite 1250 N Tustin Ave Anaheim CA 92807 www econolite com support 01100 00200 00030 rev H07 Copyright 2021 Econolite All rights reserved...

Reviews: