background image

18

Routine Maintenance

Floor Drain

FIG. 36

Wood Block

FIG. 35

Cap

O-ring Seal

Screen Support

Screen

Gasket

*Flow Plug (HVDC)

Housing

Ferrule

Nut

Cone Screen

*Flow Plug

*Install with lettered

side up, concave

side down.

CLEANING THE NOZZLE & VENTURI

A clean nozzle & venturi (See Figure 35) is a necessity

for the water treatment system to work properly.  This

small component creates the suction to move brine

from the brine tank, into the resin tank.  If it should

become plugged with sand, silt, dirt, etc., the system

will not work, and hard water will result.

Nozzle & Venturi Disc

IMPORTANT: Be sure small hole in the gasket is cen-

tered directly over the small hole in the nozzle & ven-

turi housing.  Be sure the numbers are facing up.

To get access to the nozzle & venturi, remove the

water treatment system’s top cover.  Put the bypass

valve(s) into the bypass position.  Be sure the system

is in soft water (service) cycle (no water pressure at

nozzle & venturi).  Then, holding the nozzle & venturi

housing with one hand, un screw the cap.  Do not lose

the o-ring seal.  Lift out the screen support and screen.

Then, remove the nozzle & venturi disc, gasket and

flow plug(s).  Wash the parts in warm, soapy water

and rinse in fresh water.  Be sure to clean both the top

and bottom of the nozzle & venturi disc.  If needed,

use a small brush to remove iron or dirt.  Do not

scratch, misshape, etc., surfaces of the nozzle & ven-

turi.
Gently replace all parts in the correct order.  Lubricate

the o-ring seal with silicone grease and locate in place.

Install and tighten the cap by hand, while supporting

the housing.  Overtightening may break the cap or

housing.  Put the bypass valve(s) into service (soft

water) position.
Recharge the water treatment system to reduce water

level in the tank.  This will also assure that the system

is completely recharged and ready to provide softened

water again.  Check the water level in the tank by look-

ing down the brinewell.  If the water level does not

drop after a recharge, the problem has not been

resolved.  Call 1-800-693-1138.

PROTECT THE WATER TREATMENT SYS-

TEM FROM FREEZING

If the water treatment system is installed where it could

freeze (summer cottage, lake home, etc.), you must

drain all water from it to stop possible freeze damage.

To drain the system:

1

. Close the shut-off valve on the house main water

pipe, near the water meter or pressure tank.

2

. Open a faucet in the treated water pipes to vent

pressure in the system.

3

. Move the stem in the single bypass valve to bypass.

Close the inlet and outlet valve in a 3 valve bypass

system, and open the bypass valve.  If you want

water in the house pipes again, reopen the shut-off

valve on the main water pipe.

4

. Unplug the power supply at the wall outlet.  Slide

open the salt lid and remove the water treatment

system’s top cover.  Take off both drain hoses if they

will interfere with moving the system into position

over the drain.

5

. Carefully remove the large holding clips at the water

treatment system inlet and outlet.  Separate the sys-

tem from the plastic installation adaptors, or from

the bypass valve.

6

. Lay a piece of 5 cm thick board near the floor drain

(See Figure 36).

7

. Move the water treatment system close to the drain.

Slowly and gently, tip it over until the rim rests on

the wood block with the inlet and outlet over the

drain.  Do not allow the system’s weight to rest on

the inlet and outlet fittings or they may break.

8

. Tip the bottom of the water treatment system up a

few centimeters and hold until all water has drained.

Leave the system laying like this until you are ready

to use it.  Plug the inlet and outlet with clean rags to

keep dirt, bugs, etc. out.

Summary of Contents for EPHY

Page 1: ... number of your product found on the rating decal located on the rim below the salt lid hinges System tested and certified by the Water Quality Association against CSA B483 1 Model EPHY System tested and certified by NSF International against NSF ANSI Standard 42 for the reduction of chlorine taste and odor and Standard 44 for hardness reduction efficiency and the reduction of barium and radium 22...

Page 2: ...be operated at a sustained maximum service flow rate greater than its listed rating This system has been proven to deliver soft water for at least ten continuous minutes at the rated service flow rate The rated salt efficiency is measured by lab oratory tests described in NSF ANSI Standard 44 These tests represent the maximum possible efficiency that the system can achieve Operational efficiency i...

Page 3: ...rvice Flow Rate 6 5 gpm 24 6 lpm Amount of High Capacity Ion Exchange Resin 0 94 cu ft 26 6 liters Pressure Drop at Rated Service Flow 12 8 psig Water Supply Max Hardness 95 gpg Water Supply Max Clear Water Iron 3 ppm Water Pressure Limits min max 20 100 psi 1 4 7 0 kg cm2 Water Temperature Limits min max 40 100 F 5 38 C Minimum Water Supply Flow Rate 3 gpm 11 4 lpm Maximum Drain Flow Rate 2 gpm 7...

Page 4: ...only grounded and properly protected by an overcurrent device such as a circuit breaker or fuse Do not use this system to treat water that is microbiologically unsafe or of unknown quality without adequate dis infection upstream or downstream of the system European Directive 2002 96 EC requires all electrical and electronic equipment to be disposed of accord ing to Waste Electrical and Electronic ...

Page 5: ... After the water stands for a period of time the particles settle to the bottom of the container Generally these irons are removed from water by filtra tion Chlorination is also recommended for bacterial iron Colloidal and inorganically bound iron is of ferric or fer rous form that will not filter or exchange out of water This water treatment system will not remove colloidal iron In some instances...

Page 6: ...stem close to the water supply inlet and upstream of all other plumbing connections except outside water pipes Outside faucets should remain on hard water to avoid wasting treated water and salt A nearby drain is needed to carry away regenera tion discharge drain water Use a floor drain laundry tub sump standpipe or other options check your local codes See Air Gap Require ments and Valve Drain Req...

Page 7: ...m O D Tube not included Cut barbs from drain fit ting pull clip to remove fitting from valve FIG 7 FIG 8 SINGLE BYPASS VALVE Pull out for Service Treated water Push in for Bypass 3 VALVE BYPASS From Water Treatment System To Water Treatment System Inlet Valve Outlet Valve Bypass Valve FIG 5 1 4 NPT Thread Barbs for 9 5 mm I D Tubing Drain Hose Hose Clamp INLET OUTLET PLUMBING OPTIONS Always instal...

Page 8: ...t it on a solid level surface IMPORTANT Do not place shims directly under the salt storage tank to level the system The weight of the tank when full of water and salt may cause the tank to fracture at the shim 2 Visually check and remove any debris from the water treatment system valve inlet and outlet ports 3 Make sure the turbine assembly spins freely in the out port of the valve See Figure 10 4...

Page 9: ...atment system valve inlet side NOTE Inlet and outlet are marked on the water treat ment system valve Trace the water flow direc tion to be sure hard water is to inlet IMPORTANT Be sure to fit align and support all plumbing to prevent putting stress on the water treatment system valve inlet and outlet Undue stress from mis aligned or unsupported plumbing may cause damage to the valve Complete the i...

Page 10: ...nd be sure all wiring is away from the valve gear and motor area which rotates during regenerations 1 Plug the water softener s power supply into an elec trical outlet that is not controlled by a switch and is approved by local codes NOTE The water heater is filled with hard water and as hot water is used it will refill with treated water In a few days the hot water will be fully treated To have f...

Page 11: ...e sanitiz ing bleach into and through the water softener Any air remaining in the unit is purged to the drain 4 After the recharge has completed fully open a cold water faucet downstream from the softener and allow 190 liters of water to pass through the system This should take at least 20 minutes Close the faucet Recommended by the Water Quality Association On some water supplies the unit may nee...

Page 12: ...nnected to electrical power the light on the control panel will operate as follows Light flashing with the time of day shown in the display The salt monitor system indicates a low salt level and needs to be set See Set Salt Level on Page 13 Light flashing with CLEAn flashing in the display See Fig 17 Four months have elapsed on the system s timer since start up or the last reset This is a reminder...

Page 13: ...ton once again to display a flashing 2 00AM and the words SET RECHARGE TIME This is a good time for the recharge to start in most households because water is not in use FIG 20 SET SALT LEVEL The water treatment system has a low salt indicator light to remind you to refill the storage tank with salt NOTE You must set salt level each time salt is added to the water softener To set this monitor syste...

Page 14: ...r heater will refill with bypass hard water RECHARGE TONIGHT If you do not want to start an immediate recharge but would like an extra recharge at the next preset recharge time do the following to schedule a recharge 1 Press and release do not hold the RECHARGE button The words RECHARGE TONIGHT flash in the dis play and the water treatment system will recharge at the next preset recharge time If y...

Page 15: ...ver you can adjust this time from 1 to 15 minutes in length To change this cycle time 1 Press and hold the SELECT button until the screen in Figure 27 is displayed 2 Press the SELECT button three times to display the Set Clean Time screen See Figure 29 2 Press the SELECT button twice again so that SET CLEAN OFF or SET CLEAN ON flashes in the display See Figure 28 15 SET SALT EFFICIENCY When this f...

Page 16: ...efault setting To change this setting 1 Press and hold the SELECT button until the screen in Figure 24 is displayed 2 Press the SELECT button four times so that 12 hr or 24 hr flashes in the display See Figure 30 FIG 30 FIG 32 Top Distributor Cleansing Screen Resin Tank FIG 33 ADJUSTABLE FAST RINSE To change the length of the Fast Rinse 1 Press and hold the SELECT button until the screen in Figure...

Page 17: ... age level lower and to refill more often to avoid salt bridging Recommended Salt Nugget pellet or coarse solar salts with less than 1 impurities Salt Not Recommended Rock salt high in impurities block granulated table ice melting ice cream making salts etc BREAKING A SALT BRIDGE Sometimes a hard crust or salt bridge forms in the brine tank It is usually caused by high humidity or the wrong kind o...

Page 18: ...ce water level in the tank This will also assure that the system is completely recharged and ready to provide softened water again Check the water level in the tank by look ing down the brinewell If the water level does not drop after a recharge the problem has not been resolved Call 1 800 693 1138 PROTECT THE WATER TREATMENT SYS TEM FROM FREEZING If the water treatment system is installed where i...

Page 19: ...m Contact a licensed plumber 6 Brine float dirty or broken Clean or replace Brine Valve Float Assembly 7 Leak between valve and resin tank Replace o rings between resin tank and valve Water hard some times 1 Incorrect time set Check and change time setting 2 Incorrect water hardness set Refer to Set Water Hardness section to set correctly 3 Incorrect model code programmed Refer to Program the Wate...

Page 20: ...e water is in contact with the salt and not separated by a salt bridge See Breaking A Salt Bridge section 5 While in this diagnostic screen the following infor mation is available and may be beneficial for vari ous reasons This information is retained by the computer from the first time electrical power is applied to the electronic controller a Press the p UP button to display the number of days t...

Page 21: ...b ing or brine valve riser pipe 2 After observing fill press the RECHARGE button to move the system s valve into the brine position A slow flow of water to the drain will begin Verify brine draw from the brine tank by shining a flash light into the brinewell and observing a noticeable drop in the liquid level This may take 15 to 20 minutes NOTE Be sure water is in contact with the salt and not sep...

Page 22: ...22 Water Treatment System Exploded View 8 7 6 5 26 28 15 16 18 19 20 11 22 23 24 25 8 6 3 9 10 7 5 2 1 21 14 13 17 27 12 Valve Assembly See Pages 24 25 for parts 70 71 72 4 ...

Page 23: ...Decal 16 7331834 Repl Electronic Control Board PWA 17 7351054 Power Supply 24V DC 18 7155115 Cover Brinewell 19 7338145 Brinewell 7332204 Brinewell Mounting Hardware Kit includes Key Nos 20 22 20 á Wing Nut 1 4 20 21 á Spacer 19 1 mm long 22 á Screw 1 4 20 x 15 9 mm 7331258 Overflow Hose Adaptor Kit includes Key Nos 23 25 23 á Adaptor Elbow 24 á Grommet 25 á Hose Clamp 26 7310202 Brine Valve Assem...

Page 24: ...24 Valve Exploded View 51 50 52 53 55 56 59 58 57 60 61 66 67 62 63 64 68 69 70 71 75 65 76 77 79 78 80 81 82 Wear Strip Seal Cross section View 83 84 85 86 87 88 89 90 54 72 73 74 ...

Page 25: ... Turbine Support Assembly including 2 O Rings See Key No 72 1 ea of Key Nos 73 74 73 á Turbine Support Shaft 74 á Turbine 75 7082053 Valve Body 76 7081201 Retainer Nozzle Venturi 77 7342649 O Ring 6 4 x 9 5 mm pack of 2 78 1202600 Nut Ferrule 7257454 Nozzle Venturi Assembly includes Key Nos 76 77 79 87 79 7081104 Housing Nozzle Venturi 80 7095030 Cone Screen 81 1148800 Flow Plug 1 1 lpm 82 7114533...

Page 26: ... unusual force of nature such as but not limited to flood hurri cane tornado or earthquake Warrantor is excused if failure to perform its warranty obligations is the result of strikes government regulation materials shortages or other circumstances beyond its control THERE ARE NO WARRANTIES ON THE WATER TREATMENT SYSTEM BEYOND THOSE SPECIFICALLY DESCRIBED ABOVE ALL IMPLIED WARRANTIES INCLUDING ANY...

Reviews: