EN Series Precision Air Conditioner Owners Manual
Installation Piping Calculate Oil Charge
30
Ecosaire
®
July 2009
Data subject to change without notice.
Air-Cooled Direct-Expansion and Air-Cooled DualCool Units Only
Some installations may require the addition of extra
refrigeration oil.
1. Note the compressor model from the compressor
nameplate. If it is not a Copeland brand, please
contact Ecosaire.
2. Note the type of oil to be added from the compressor
nameplate. Copy this type into BOX C on page 32.
3. Add 1 fluid ounce of oil for every 5 pounds of refrigerant
over 20 pounds.
BOX A - 20 lb =
(BOX A1) / 5 lb =
Prepare to add this many ounces of the type of oil specified
on the compressor nameplate.
Copy this amount into BOX B on page 32.
BOX A
BOX A1
BOX B
pounds of refrigerant