REQUIRED GLYCOL FLOWS
Outdoor
Temp. 95°F
Outdoor
Temp. 100°F
Glycol-Cooled
Direct
Expansion
or
Glycol-Cooled
DualCool
or
FreeCool
Model No.
EN-27
EN-35
EN-42
EN-51
EN-68
EN-79
EN-87 EN-102
40.9
34.8
107.8
91.3
72.5
60.8
53.8
155
132
GPM
lpm
GPM
lpm
408
346
274
230
204
40.9
34.8
107.8
91.3
72.5
60.8
53.8
155
132
408
346
274
230
204
81.4
308
81.4
308
Startup Check Remote Heat Exchanger Operation
Glycol-Cooled Direct Expansion, Glycol-Cooled DualCool,
& FreeCool Units Only
(continued from previous page)
Check that the glycol solution is flowing at the proper flow rate. See table below.
After the pump(s) run for a while, residual air may be removed. Check that the system is still full of glycol
solution.
Turn off the electrical power to the remote heat exchanger.
Remove the jumper from step 2 (previous page).