Temperature Set Points Pre-Startup Adjustments Startup
Press
↵
↵
to store the new set point. The cursor moves to the top left corner.
To
change the temperature set point
, press either
↑↑
or
↓↓
to select the desired
temperature. The longer the button is held, the faster the set point changes.
To adjust the temperature set point screen, first press
Prg
, enter the password,
and press
↵
↵
, as discussed in
Startup - Pre-startup Adjustments - Controller
Password
. The screen will appear as shown.
Note: This adjustment requires the user password, see Startup - Pre-startup
Adjustments - Controller Password.
Press
↓↓
to access
Temperature Set Pts
.
Press
↵
↵
to move the cursor to the set point.
To access the
temperature alarm set point
screen, press
↓↓
twice.
Press
Prg
,
enter the password
, and press
↵
↵
,
as discussed in
Startup - Pre-start-
up Adjustments - Controller Password
. The screen will appear as shown.
The temperature alarms are factory set for High=80oF and Low=60oF. If the room temperature goes over
“High” or under “Low” for a period greater than “Delay”, an alarm will be registered. Unit operation will not be
affected. These settings can be changed as below.
To
select the alarm set point to change
, press
↵
↵
repeatedly to move the cursor to
the desired position. The example is for low temperature alarm set point.
To
change the set point
, press either
↑↑
or
↓↓
.
To
store the new value
, press
↵
↵
repeatedly to move the cursor back to the top left
corner.
ST
ARTUP