Adjust Head Pressure Air-Cooled Direct Expansion Units Only
Owners Manual Ecosaire
®
EN Series Precision Air Conditioner
Adjustments Startup
Ecosaire
®
July 2009
61
Data subject to change without notice.
Locate the remote air-cooled condenser. Be sure the temperature
of the ambient air is less than the rating of the condenser.
For each refrigeration circuit:
With the compressor running, check that the refrigerant sight
glass is full.
Check the suction pressure and the discharge pressure at the
compressor. The suction pressure should be above 50 PSI. If it
is not above 50 PSI, stop and determine the cause.
The discharge pressure should be 250 PSI ± 15 PSI. If it is
not, then:
ST
ARTUP