20
CONTROL VALVE PROGRAMMING AND COVER DRAWING MANUAL
This manual is the intellectual property of Ecosoft. Copying and reprinting is prohibited. © 2021
DIAGNOSTICS
STEP 1D
Diagnos�cs
STEP 1D – Press
▲
and
▼
simultaneously for three seconds. If screen in step 2D does not appear
in 5 seconds the lock on the valve is ac�vated.
To unlock press
▼
, NEXT,
▲
, and CLOCK in
sequence, then press
▲
and
▼
simultaneously for 3 seconds.
STEP 2D
– Days, since last regenera�on:
This display shows the days since the last regenera�on
occurred. Press NEXT
to go to Step 3D. Press REGEN to exit Diagnos�cs.
STEP 3D – V
olume, since last regenera�on:
This display shows the volume of water that has been
treated since the last regenera�on.
This display will equal zero if a water meter is not installed.
Press NEXT to go to Step 4D. Press REGEN to return to previous step.
STEP 4D – Reserve History V
olume used for last 7 days: If the valve is set up as a so�ene
r, a
meter is installed and Set Volume Capacity is set to “Auto,” this display shows 0 day (for today)
and the reserve capacity. Pressing
▲
will show day 1 (which would be yesterday) and the reserve
capacity used. Pressing
▲
again will show day 2 (the day before yesterday) and the reserve
capacity. Keep pressing
▲
to show the capacity for days 3, 4, 5 and 6.
▼
can be pressed to move
backwards in the day series. This screen is not displayed if
fi
lter
, �me clock, meter immediate,
alternator or volume override regenera�on is selected. Press NEX
T
at any �me to go to Step 5D.
Press REGEN to return to previous step.
STEP 5D - V
olume, 63-day usage history:
This display shows day 0 (for today), day 1 (for
yesterday), etc., and the volume of water treated that day. Press
▲
to show the volume of water
treated for the last 63 days. If a regenera�on occurred on the day the le�er “R” will also be
displayed. This display will show dashes if a water meter is not installed. Press NEXT
at any �me
to go to Step 6D. Press REGEN to return to previous step.
STEP 6D - Tank Transfer History. Only displayed when 1.0TWIN is selected in Step 2CS. Use
▲
or
▼
to scroll through the last 10 tank transfers. “1”= transfer number – 10 transfers maximum.
“A” = tank transferring. “3 DAYS” = days ago of transfer – 99 days maximum. “0.00 m
3
” = M
3
used at �me of tank transfe
r
. “13:35” = �me of transfe
r.
Press NEXT to go to Step 7D. Press REGEN to return to previous step.
STEP 2D
STEP 3D
STEP 4D
STEP 5D
STEP 6D