09.06.2017 Rev. 08
31
TECHNICAL DATA
Capacity Table
Min.
kcal/h
Max.
kcal/h
Min.
kW
Max.
kW
Min.
Nm
3
/h
Max.
Nm
3
/h
Min.
kcal/h
Max.
kcal/h
Min.
kW
Max.
kW
Min.
kg/h
Max.
kg/h
kW
kW
VAC
ECO 50 K L C 2
215.000
1.290.000
250
1.500
26,1
156,4
337.750
1.351.000
393
1.571
33,1
132,5
2,20
0,75
3N 380
ECO 55 K L C 2
258.000
1.720.000
300
2.000
31,3
208,5
386.000
1.737.000
449
2.020
37,8
170,3
3,00
0,75
3N 380
ECO 55 K L C 2a
258.000
2.150.000
300
2.500
31,3
260,6
386.000
2.123.000
449
2.469
37,8
208,1
3,00
0,75
3N 380
ECO 60 K L C 2
369.800
2.580.000
430
3.000
44,8
312,7
598.560
2.580.000
696
3.000
58,7
252,9
4,00
0,75
3N 380
ECO 65 K L C 2
430.000
3.010.000
500
3.500
52,1
364,8
733.580
3.010.000
853
3.500
71,9
295,1
5,50
0,75
3N 380
ECO 70 K L C 2
498.800
3.500.200
580
4.070
60,5
424,3
916.760
3.500.200
1.066
4.070
89,9
343,2
7,50
0,75
3N 380
ECO 50 K L C 3
215.000
1.290.000
250
1.500
26,1
156,4
337.750
1.351.000
393
1.571
33,1
132,5
2,20
0,75
3N 380
ECO 55 K L C 3
258.000
1.720.000
300
2.000
31,3
208,5
386.000
1.737.000
449
2.020
37,8
170,3
3,00
1,10
3N 380
ECO 55 K L C 3a
258.000
2.150.000
300
2.500
31,3
260,6
386.000
2.123.000
449
2.469
37,8
208,1
3,00
1,10
3N 380
ECO 60 K L C 3
369.800
2.580.000
430
3.000
44,8
312,7
598.560
2.580.000
696
3.000
58,7
252,9
4,00
1,10
3N 380
ECO 65 K L C 3
430.000
3.010.000
500
3.500
52,1
364,8
733.580
3.010.000
853
3.500
71,9
295,1
5,50
1,50
3N 380
ECO 70 K L C 3
498.800
3.500.200
580
4.070
60,5
424,3
916.760
3.500.200
1.066
4.070
89,9
343,2
7,50
1,50
3N 380
ECO 75 K L C 3
686.000
4.800.000
798
5.581
83,2
581,8
1.003.620
4.824.600
1.167
5.610
98,4
473,0
11,00
1,50
3N 380
FAN
MOTOR
POWER
MAIN
SUPPLY
GAS
CAPACITY
LIGHT OIL
CAPACITY
GAS-LIGHT OIL DUAL BURNERS CAPACITY TABLE
BURNER TYPE
GAS
CAPACITY
NATURAL GAS
CONSUMPTION
LIGHT OIL
CAPACITY
LIGHT OIL
CONSUMPTION
MODULATING GAS-LIGHT OIL DUAL BURNERS
OIL PUMP
POWER
TWO STAGE GAS-LIGHT OIL DUAL BURNERS
H
u
Natural Gas =8250 kcal/Nm
3
H
u
Light Oil (L) = 10200 Kcal/kg
Summary of Contents for ECO 50 K L C 2
Page 10: ...09 06 2017 Rev 08 9 Burner Components ECO 50 KLC2...
Page 12: ...09 06 2017 Rev 08 11 ECO 55 KLC2 2a...
Page 14: ...09 06 2017 Rev 08 13 ECO 60 KLC2...
Page 16: ...09 06 2017 Rev 08 15 ECO 65 KLC2...
Page 18: ...09 06 2017 Rev 08 17 ECO 70 KLC2...
Page 20: ...09 06 2017 Rev 08 19 ECO 50 KLC3...
Page 22: ...09 06 2017 Rev 08 21 ECO 55 KLC3 3a...
Page 24: ...09 06 2017 Rev 08 23 ECO 60 KLC3...
Page 26: ...09 06 2017 Rev 08 25 ECO 65 KLC3...
Page 28: ...09 06 2017 Rev 08 27 ECO 70 KLC3...
Page 30: ...09 06 2017 Rev 08 29 ECO 75 KLC3...
Page 33: ...09 06 2017 Rev 08 32 Back Pressure Capacity Diagrams...
Page 34: ...09 06 2017 Rev 08 33 Burner Dimensions...
Page 36: ...09 06 2017 Rev 08 35...
Page 37: ...09 06 2017 Rev 08 36...
Page 49: ...09 06 2017 Rev 08 48 MB ZRD LE 405 412 Series Gas Valve...