Seismic Restraint
All installation scenarios for Monica Plus require the use of hold-down anchors (one on each side).
Fixing to Concrete Floor:
•
Minimum M8 expansion anchors (M10 recommended) or min M8 epoxy- set anchors.
•
Approved Anchors: Expansion Anchors-Ramset Dynabolt and Trubolt, Hilti HAS.
•
Epoxy-set Anchors – Ramset Epcon, Ramset Chemset and Hilti HVU.
2.10 Fixing to Timber Floor Framing
Minimum 14g x 60 screws (6.3mm diameter) or M10 X 90 coach-screws. These shall be fixed a minimum
of 40mm into the centre-line of the existing floor joists. If screws cannot be installed directly into an
existing floor joist, solid blocking between joists (min size 90x45) shall be provided.
2.11 Installation
Monica Plus should be installed in a centrally located position within the home. This will assist the
appliance to perform to the level required. As Monica Plus heats space by convecting air through heat
exchange tubes, the heater should face the area the majority of the area to be heated.
Monica Plus requires a power source to function. This is standard mains feed 240v plug-if this is
unavailable in close proximity a grounded extension lead may be used.
Monica Plus is to be installed on a non-combustible surface which must have a forward projection of a
minimum of 150mm from the glass door.
Ensure all 75mm flue joins are sealed with a high temp silicon (Maniseal).
Please check all clearances to combustibles as listed on page 30 of this Owners’/Technical manual.
In accordance with the requirements of AS/NZS 2918:2001 Monica Plus must be secured by seismic
restraint.