The LED indicator, pos 8, shows that blocking thermostat is switched on. When the cause is
eliminated, the block system is recovered manually
. T
he control panel connects to the main
board by a 20 wire cable through the cuplung X5.
The mainboard is joined by the individual elements shown in respective power wires
arrangement. When replacing the boiler sensor or mainboard, but not replace the sensor, it is
possible to obtain the temperature difference. In case that the management is used for
example for electric boiler, then it is not required to be mounted room thermo regulator. In
this case jumper J1, which placed on the main board is switched to pos 2 and by trimmer
potentiometer W pos 12 the temperature is set. In all other cases jumper J1 is placed in pos. 1
4.2. TECHNICAL CHARACTERISTICS
Power Supply
240V/АС
Maximum permissible operating current of the power relays
16А / 250V
The outlet electricity of the room thermo regulator corresponding to the set
temperature of the water in the boiler 20 to 90 С
4 до 20mА
Protection against overheating. Digital indicators for the set and the current
temperature. Smooth loading of the power supply network.
Temperature measurement accuracy
+-3º С