background image

6

INSTALLATION - FEED WATER SUPPLY

REJECT WATER DRAIN FITTING

Check and comply with local plumbing codes

as you

plan, then install a cold feed (supply) water fitting. The

fitting must provide a leak tight connection to the RO

1/4" OD tubing, see Figure 6, Page 10. A typical installa-

tion, using standard plumbing fittings is shown in Figure

1. A saddle valve (not available from EcoWater) may be

used where codes permit. Installation instructions are on

Page 22.

NOTE:

Codes in the state of Massachusetts require

installation by a licensed plumber, and do not permit the

use of the drain clamp. For installation, use plumbing

code 248-CMR of the Commonwealth of Massachusetts.

PIPE FITTINGS

(compression shown)

IMPORTANT:

Before starting, close the hot and cold

water shutoff valves (See Figure 1). Use a pan to catch

water when disassembling the pipe.
Complying with plumbing codes, install a fitting on the

kitchen cold water pipe to adapt 1/4" OD tubing. A typi-

cal connection is shown in Figure 1. You can use solder

or threaded fittings. If threaded fittings are used, be sure

to use pipe joint compound or Teflon tape on outside

threads.
Do not connect the tubing to the fitting until Step 2, top

of Page 10.

Running the RO drain tubing directly to a floor drain,

laundry tub, sump, standpipe, etc., is preferred. If that is

not possible or practical, check and comply with local

plumbing codes as you plan, then install a drain fitting

for RO reject water. This fitting is usually installed at the

sink p-trap (always above). It must provide a leak-tight

connection to 3/8" OD tubing from the RO product water

faucet airgap, see Figure 6, Page 10. Typical drain fitting

installations are listed below. A drain adapter (part no.

7192230) is available to use where codes permit.

Installation instructions are on Page 22. Other options are

shown on Page 25.

“Y” BRANCH TAIL PIECE, OR OTHER

APPROVED P-TRAP DRAIN

Reject water from the RO is routed to the RO faucet air-

gap (1/4" tubing), then to the drain point with 3/8" OD

tubing. COMPLYING WITH PLUMBING CODES,

install a fitting to accept the 3/8" tubing. Figure 2 shows

typical p-trap and "Y" branch tail piece type drains.
Do not connect drain tubing until Step 1, top of Page 10.

FIGURE 1

FIGURE 2

WATER SUPPLY TYPICAL CONNECTION

(using compression fitting)

hot water

shutoff

cold water

shutoff

cold

water pipe

1/4” compression fitting

insert

ferrule

1/4” green tubing

from RO inlet

DRAIN TYPICAL CONNECTION

(check local codes)

“Y” branch 

tailpiece drain

other approved

p-trap drain

3” minimum

Summary of Contents for ERO-385

Page 1: ...85E HERO 385Plus Designed Engineered Assembled in the U S A Systems tested and certified by NSF International against NSF ANSI Standards 58 and 42 for the reduction of claims as specified in the perfo...

Page 2: ...eriod of five 5 years from defects in material and workmanship The faucet will be guaranteed for a period of three 3 years from defects in material and workmanship The reverse osmosis membrane will be...

Page 3: ...data sheet and Arsenic Facts section for an explanation of reduction performance u NOTE This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part...

Page 4: ...ature and total dissolved solids Efficiency rating means the percentage of the influent water to the system that is available to the user as revers osmosis treated water under operating conditions tha...

Page 5: ...quired or a special drain adapter are avail able from EcoWater to use where codes permit Refer to Pages 22 and 25 These options install on the sink drain pipe tailpiece above the p trap RO FAUCET The...

Page 6: ...g to the fitting until Step 2 top of Page 10 Running the RO drain tubing directly to a floor drain laundry tub sump standpipe etc is preferred If that is not possible or practical check and comply wit...

Page 7: ...rough the sink or countertop hole and through the spacer if used Figure 3 NOTE If you will route the RO drain tubing directly to the drain point disregard Steps 4 and 6 and do Step 1 on top of Page 10...

Page 8: ...si tion the tank upright or on its side 5 Apply teflon tape on the tank nipple threads and install the shutoff valve 6 Model ERO 385E only Connect telephone style wire from the monitored faucet to the...

Page 9: ...e o ring Continue pushing until the tube bottoms out against the back of the fitting A common mistake is to stop pushing when the tube engages the o ring This will lead to future leaks When a 1 4 tube...

Page 10: ...ring as required pages 6 and 22 Or connect RO drain tubing if using floor drain or other approved drain point Route the 1 4 red tubing from the RO to the floor drain sump etc Be sure to pro vide an ai...

Page 11: ...ure 6 6 Sanitizing the system will be completed during the pressure test and purging steps below NOTE The bleach must be removed from the system before drinking the water See purging instructions belo...

Page 12: ...manifold assembly RO electronics receptacle FIGURE 7 Plug into receptacle Wire from faucet Plugged into receptacle INSTALLING OR REPLACING BATTERIES Model HERO 385Plus Only 3 Batteries AAA size Batter...

Page 13: ...t will then turn green after the system has been registered LED Indication Status Red 3 sec Batteries are too low to place unit into Connect Mode Flashing Amber up to 2 minutes System is in Connect Mo...

Page 14: ...nd that alert to EMAIL or TEXT When finished setting up alerts click NEXT 6 DASHBOARD Following successful completion of the connec tion procedure the new RO system s dashboard will be displayed with...

Page 15: ...display data items from the RO system DATA ITEMS updated daily between 2 00 2 59 AM TDS Removal Percentage Total dissolved solids reduction from inlet to outlet as a percentage Filter Life Re maining...

Page 16: ...d filters are good Amber Warning filters need replacing Filters need replacing when water has been drawn after 6 months time or 650 gallons 2 460 L have been used Red RO membrane needs to be replaced...

Page 17: ...the same efficiency and contami nant reduction performance The life of the RO membrane cartridge depends mostly on the pH and hardness of the supply water to the RO system see specifications Cartridg...

Page 18: ...order post filter Reverse Osmosis and then prefilter Turn cartridges to the right to re attach to the filter heads 6 Model ERO 385E only replace the battery with new CR 2032 or equivalent 7 On the ERO...

Page 19: ...go on steady then flick er then go off for 6 seconds See chart at right When the LED begins to blink after button has been held down for about 12 seconds immediately release the but ton 3 Once the but...

Page 20: ...lace the prefilter postfilter and RO membrane cartridges flow control and screen Water leaking from faucet airgap hole Drain side of faucet airgap 3 8 tubing plugged restricted or incorrectly connecte...

Page 21: ...flows to the storage tank 5 Waste water with dissolved solids leave the Reverse Osmosis membrane and flows to the drain 6 Faucet is activated 7 Processed water leaves the storage tank and flows to th...

Page 22: ...drain pipe The adapter installs directly onto the sink tailpiece as typically shown in Figure 21 Locate so drain tubing from the faucet makes a straight run to the adapter without dips loops low spots...

Page 23: ...rap drain adapter Check your local codes Always be sure to provide an air gap between the end of the hose and the drain point of 2 pipe diameters or 1 inch whichever is larger Telephone cable extensio...

Page 24: ...24 REPAIR PARTS 12 10 11 14 15 17 18 5 3 2 1 30 29 4 19 20 24 26 25 28 27 9 8 7 13 16 22 23 21 23 31 6 1 4 red drain tubing...

Page 25: ...scription 7333137 Check Valve Kit includes Key No 20 2 of Key No 19 19 O Ring Auto Shutoff Cover 2 req d 20 Check Assembly 7333179 Diaphragm Kit includes Key Nos 21 22 2 of Key No 23 21 Spacer Ring 22...

Page 26: ...pper 3 0 mg L 10 1 3 mg L 98 8 Pass Cysts 50 000 particles mL 99 95 99 99 Pass Lead 0 15 mg L 10 0 010 mg L 99 1 Pass Fluoride 8 0 mg L 10 1 5 mg L 96 5 Pass Nitrate plus Nitrite as N 30 mg L 10 10 0...

Page 27: ...98 Dibromoacetonitrile NA 24 g L 0 6 g L 98 Dichloroacetonitrile NA 9 6 g L 0 2 g L 98 Trichloroacetonitrile NA 15 g L 0 3 g L 98 Haloketones HK 1 1 dichloro 2 propanone NA 7 2 g L 0 1 g L 99 1 1 1 t...

Page 28: ...upplies that have been demonstrated to contain only pentavalent arsenic Treatment with chloramine combined chlorine is not sufficient to ensure complete conversion of trivalent arsenic to pentavalent...

Page 29: ...water These models will not convert trivalent arsenic to pentavalent arsenic If you have free chlorine residual in contact with your water supply for at least one minute any trivalent arsenic will be...

Reviews: