Use piping materials and joining methods acceptable
•
to authority having jurisdiction. In absence of such
requirements:
USA - National Fuel gas Code, ANSI Z223.1/NFPA 54
•
Canada - Natural Gas and Propane Installation Code,
•
CAN/CSA B149.1
Size and install gas piping system to provide suffi cient
•
gas supply to meet maximum input at not less than
minimum supply pressure. See Table 5.
Support piping with hooks straps, bands, brackets,
•
hangers, or building structure components to prevent or
dampen excessive vibrations and prevent strain on gas
connection. Boiler will not support piping weight.
Use thread (joint) compound (pipe dope) suitable for
•
liquefi ed petroleum gas.
Provide sediment trap up stream of gas valve.
•
7.2 Conversion Kit Instructions
See Gas Conversion Kit Instructions included with Boiler.
•
CAUTION
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
•
Do not touch any electrical switches; do not use
•
any phones in your building.
Immediately call your gas supplier from
•
a neighbor’s phone.
Follow gas supplier’s
instructions.
If you cannot reach your gas supplier, call the fi re
•
department.
!
!
7 - GAS SUPPLY PIPING
TABLE 5: GAS SUPPLY PRESSURE
SIZE
Maximum
Input (Btuh)
Natural Gas
Propane
Min.
Max.
Min.
Max.
075/100
75,000
3.0" w.c.
(0.7 kPa)
13.5" w.c.
(3.3 kPa)
5.0" w.c.
(1.2 kPa)
13.5" w.c.
(3.4 kPa)
Bottom cover
for Optional Gas
Connection
7-1 Gas Connection Knockout Plate at Bottom of
Boiler
7-3 Bottom Gas Connection
Optional Bottom Gas
Connection
7-2 Gas connection at Top of Boiler
Gas Connection Top
of Boiler
Note: See Glossary - Piping Table 16