29
8 - ELECTRICAL CONNECTIONS
Domestic Hot Water (DHW) Thermostat, if used.
•
Use temperature control with dry contacts rated
A.
at 0.5 amps @ 120 VAC. Boiler control does not
provide power to DHW temperature control.
NOTICE
IMPORTANT: Do not apply power to DHW T-T
terminals. Dry contact only, use of isolation relay
may be necessary.
Maximum wire length is 330 ft (100 m) 22 gauge
B.
wire.
Connect wires (interchangeable) to low voltage
C.
terminal plug DHW T-T terminals. Wires are
interchangeable.
Central Heating Thermostat
•
Use thermostat or boiler system control with dry
A.
contacts related 0.5 amps @ 120 VAC.
Boiler
control does not provide 24 VAC power to central
heating thermostat.
Locate and install thermostat per manufacturer's
B.
instructions. Maximum wire length is
330 ft (100
m) for 22 ga. wire.
Connect wires to low voltage terminal plug CH T-T
C.
terminals. Wires are interchangeable.