25
Figure 13 - Side Wall Vent / Intake terminations - Less Than 12” Clearance Above Grade
Figure 14 - Side Wall Vent/Intake Terminations - 12” Or More Clearance Above Grade
COMBUSTION AIR AND VENT PIPE
Less Than 12” Clearance
12” Or More Clearance
OVERHANG
12" MINIMUM
90°
VENT
12" SEPARATION
BETWEEN BOTTOM
OF AIR INTAKE AND
BOTTOM OF VENT
MAINTAIN 12" MIN
CLEAR ABOVE HIGHEST
SNOW LEVEL OR GRADE
3"
MAXIMUM
SEPARATION
18"
MAXIMUM
15"
MAX
12"
MINIMUM
12"
MINIMUM
36" MIN
90°
BRACKET
VENT
18"
MAXIMUM
MAINTAIN 12" MIN
CLEAR ABOVE HIGHEST
SNOW LEVEL OR GRADE
12" SEPARATION
BETWEEN BOTTOM
OF AIR INTAKE AND
BOTTOM OF VENT
12" MINIMUM
OVERHANG
3"
MAXIMUM
SEPARATION
12"
MINIMUM
12"
MINIMUM
36" MIN