48
K. Reinstall burner and mixer gasket and position
mixer assembly over studs. Install
fi
ve (5) nuts but
do not tighten. Reinstall igniter and igniter gasket
and fasten with two (2) screws. Use care when
installing the igniter. Tighten
fi
ve (5) nuts holding
mixer assembly.
L. Connect:
• Gas line to gas valve
• Condensate drain line to boiler
• Pressure switch hose to gas valve
• Air by-pass to mixer
• 1 ½” x 2”
fl
exible coupling to air inlet and make
sure to put air baf
fl
e back to correct position
• Igniter wires
• Gas valve wires
3.
Visually inspect condensate lines leading from boiler
sections and vent pipe connector to condensate trap.
Refer to repair parts diagrams. Any foreign material or
debris visible in condensate lines needs to be cleaned
out as follows:
A. Disconnect condensate drain lines from condensate
trap.
B. Remove condensate trap and drain all water from
trap.
C. Disconnect condensate lines from
fi
tting on bottom
of boiler and vent pipe connector.
D. Run cold water through condensate lines and trap
to thoroughly
fl
ush out any sediment or debris.
E. Reinstall condensate trap and condensate lines.
F. Follow instructions under “Near Boiler Piping” for
fi
lling condensate trap with water.
4.
Inspection of
fl
ue connector requires following steps. Refer
to repair parts diagram.
A. Loosen the clamp on the draft inducer end of the
2” vent pipe connector that connects the vent
to the draft inducer. Disconnect (unplug) wiring
harness from draft inducer motor and draft inducer
temperature safety switch. Remove four (4) bolts
that attach draft inducer to
fl
ue connector.
B. Remove draft inducer and gasket from top of
fl
ue
connector.
C. Inspect interior of
fl
ue connector. Any buildup of
sediment or aluminum oxide on inside surface must
be cleaned. Position draft inducer gasket and draft
inducer and fasten with four (4) screws. Be sure to
connect ground wire from draft inducer motor to
one of four mounting screws.
D. Connect wiring harness leads to draft inducer motor
and draft inducer temperature safety switch.
E. Connect vent pipe connector to draft inducer outlet.
MAINTENANCE AND CLEANING
Annual Examination And Cleaning Of Boiler
Components
DANGER
Before servicing, turn off electrical power to boiler
at service switch. Close manual gas valve to turn
gas supply OFF to boiler. Failure to comply will result
in death or serious injury.
!
NOTICE
Have quali
fi
ed service agency perform the following
service procedures. Boiler owner should not attempt
these procedures.
1.
Before Servicing, turn off electrical power to boiler at
service switch. Close manual gas valve to turn off gas
supply to boiler.
2.
Cleaning Flue passages between boiler sections.
A. Any buildup of sediment or aluminum oxide (white
powdery or
fl
aky substance) in
fl
ue passages must
be cleaned as follows.
B. Remove jacket front and top panels. Disconnect
condensate drain line from barbed
fi
tting on bottom
of boiler. Keep open end of drain line above water
level in condensate trap to prevent trap from
draining. Disconnect pressure switch hose from
barbed
fi
tting on gas valve. Disconnect 1½ x 2”
fl
exible coupling from air inlet. Disconnect air by-
pass (½” transparent vinyl tube) from bottom of
mixer.
C. Remove air baf
fl
e from ½” x 2”
fl
exible coupling
and clean air baf
fl
e if necessary. Refer to repair
parts diagram, mixer and pressure switch
assembly.
D. Con
fi
rm manual gas valve is closed and disconnect
gas line to gas valve at union. Disconnect wires to
gas valve and igniter.
E. Loosen but do not remove
fi
ve (5) nuts attaching
mixer assembly to boiler. Remove two (2) igniter
screws and remove igniter.
F. Remove
fi
ve (5) nuts and remove mixer assembly.
Remove burner and mixer gasket.
G. Aluminum oxide deposits are water soluble and
may be rinsed away with spraying or running
water. Before rinsing, connect a ½” I.D. hose to
barbed
fi
tting on bottom of boiler and run hose to
bucket or drain.
H. After rinsing, remove any remaining loosened
sediment using shop vacuum with snorkel
attachment.
I. Inspect burner for any foreign matter in
fl
ame
ports or inside burner. Any foreign matter should
be removed by blowing with compressed air or
vacuuming.
J. Inspect interior of mixer for any signs of sediment
or aluminum oxide and clean if necessary.
NOTICE
Verify proper operation after servicing.
Summary of Contents for Dunkirk 4 Series
Page 33: ...33 Figure 22 Ladder Diagram for Figure 22 ELECTRICAL WIRING ...
Page 52: ...52 Troubleshooting Chart 1 TROUBLESHOOTING ...
Page 53: ...53 Troubleshooting Chart 2 TROUBLESHOOTING ...
Page 63: ...NOTES ...
Page 64: ...DUNKIRK BOILERS 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com ...