40
7.1 General
• Use piping materials and joining methods acceptable
to authority having jurisdiction. In absence of such
requirements:
• USA - National Fuel Gas Code, ANSI Z223.1/NFPA 54
• Size and install gas piping system to provide sufficient gas
supply to meet maximum input at not less than minimum
supply pressure. DMG-380 requires a gas rate of 377
ft3/h (10.7 m3/h) for Natural Gas (Gas A) and 149 ft3/h
(4.2m3/h) for Liquid Propane Gas (Gas E).
• Gas meter and supply pipes must be capable of delivering
the listed quantity of gas in addition to demand from any
other appliances in the house. DMG-380 requires a 1” (25.4
mm) gas supply pipe.
• Support piping with hooks straps, bands, brackets,
hangers, or building structure components to prevent or
dampen excessive vibrations and prevent strain on gas
connection. Boiler will not support piping weight.
• Use thread (joint) compound (pipe dope) suitable for
liquefied petroleum gas.
• Install external field sourced manual main gas shutoff
valve, ground joint union, and sediment trap upstream of
gas valve. See figure 7-2.
• Leak test boiler and gas line connections before placing
boiler into operation.
7.2 LP Conversion
• See conversion instructions included with LP Conversion
Kit. Purchased Separately.
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the fire
department.
!
FIGURE 7-1 Gas Connection
(View from Back of Boiler)
Gas
Connection
7 - GAS SUPPLY PIPING
Note
7-2- Drip Leg
Gas Supply
Pressure
Natural Gas
LP
Min
Max
Min
Max
3.0" w.c.
(0.7 kPa)
13.5" w.c.
(3.3 kPa)
5.0" w.c.
(1.2kPa)
13.5" w.c.
(3.4kPa)