33
figure 42 - Configuration Mode for CAHV Air Handlers
Item
Display Possible Value
(flashing)
overview factory
Settings
To access: Press MODE and PROG together 5 seconds, repeat to exit; automatically exits after 20 seconds idle
Temperature Setting
Scale
01 F-C
F
C
Fahrenheit
Celsius
F
Select temperature scale for display and operating settings.
Heat Source
02 HEAT
ON
OFF
Available
Not Available
See
Note 3
Set to ON if unit is equipped with electric heater option.
Electric heater is required for DRY mode operation and for
automatic changeover operation.
Heat Pump
(see Note 1)
03 H-P
ON
OFF
Available
Not Available
OFF
Set to ON if unit is built for heat pump operation and
connected to appropriate compressor unit.
Auto Changeover
Differential (ACO)
(see Note 2)
04 d-b
2
3
4
5
6
2° – 6°
2°
Auto changeover automatically operates unit in heating
or cooling based on room temperature versus setpoint.
Setting is dead band temperature:
Cooling is on while room temperature is at setpoint PLUS
dead • band.
Heating is on while room temperature is at setpoint
MINUS dead • band.
Example: setpoint = 68°F, dead band is 3°F — cooling is
on with • room temperature at or above 71°F — heating
is on with room temperature at or below 65°F.
Check Filter Time
05 F:Lt
2
5
7
10
12
250 Hours
500 Hours
750 Hours
1000 Hours
1250 Hours
10
Set time for automatic notice of time to change filter.
At end of time period, control displays FILTER CHECK
warning. Warning also appears if four evaporator freeze-
ups occur in 24-hour period.
Room Air Sampling
06 A:r
0 (OFF)
5
10
15
20
Disabled
5 minutes
10 minutes
15 minutes
20 minutes
15
During stand-by periods, room air sampling causes fan
to cycle on for period of 60 seconds at time interval
specified. Insures unit’s temperature sensor senses
accurate sampling of room air avoiding comfort problems
due to stratification.
Auto Re-Start After
Power Outage
07 A-P
ON
OFF
Enabled
Disabled
ON
Set to ON for unit to automatically restart after power
outage. Set to OFF for unit to remain off after power
outage.
Note 1 Setting 03, Heat pump, is SKIPPED if setting 02, Heat source, is OFF.
Note 2 Setting 04, Auto changeover, is SKIPPED if setting 03, Heat source, is OFF.
Note 3 Factory setting is ON if electric heat is installed in unit, or OFF if electric heat is not installed
SeTTIng THe COnTROlleR