10
4.2
Prepipe supply and return water connections with
factory fi ttings before wall mounting.
4.3 Wall Mounting
Mount boiler on wall using wall mounting bracket included
with unit.
Structure must be capable of supporting boiler weight
•
plus 60 lbs (28 kg). See Table 1, page 2.
Wall mount bracket has 4 slots allowing mounting on
•
two (2) wall studs spaced at 11½" to 16½" on center.
See fi gure 4-2.
Boiler includes (4) 3/8" x 3" lag screws and (4) washers
•
for attaching wall mount bracket to wood studs. Field
source appropriate fasteners for other wall constructions
(masonry, concrete).
Attach wall mount bracket level on wall.
•
Boiler must engage with wall mount bracket.
•
Avoid overhang on sides of wall mount bracket. Verify
•
boiler bracket is centered on wall bracket. See fi gure
4-2.
4 - LOCATING BOILER
FIGURE 4-2 Wall Mount Bracket Engaged with
Bracket on Boiler
Center brackets. Avoid
overhang on sides of wall
mount bracket.
CAUTION
Boiler weight exceeds 75 pounds (34 kg). Do not lift
boiler onto wall without assistance.
!
!
4 Slots for attaching Wall
Mount Bracket to Studs
Summary of Contents for SSC Olsen OLSSC-050
Page 46: ...46 13 TROUBLE SHOOTING ...
Page 53: ...53 14 WIRING DIAGRAM 14 1 Connection Diagram ...
Page 54: ...54 14 WIRING DIAGRAM 14 2 Schematic Diagram of Ladder Form ...
Page 71: ...71 Date Service Performed Company Name Tech Initials Company Address Phone ...
Page 72: ...ECR International Inc 2201 Dwyer Avenue Utica NY 13504 4729 web site www ecrinternational com ...