Specifications
General Performance
Operating Temperature range
0 ~ 50℃
Operating Humidity range
0 ~ 95% RH (Non-condensing)
Storage Temperature
-20℃ ~60℃
CO₂ Measurement
Sensing Method
NDIR (Non-dispersive Infrared)
Measurement Range
0 to 5,000 / 10,000ppm (Selectable by jumper),
0 to 2,000 (Optional)
Accuracy
±30ppm ±5%
Response Time(90%)
150 seconds
Sampling Interval
3 sec.
Electrical Data
Input Power
24VAC, 24VDC± 20%, 50/60Hz
(2 Power lines)
OutputConnector
4 ~ 20mA and 2 ~ 10VDC (Default)
0 ~ 10VDCand 0 ~ 20mA
(Jumper selectable
-Voltage output or current output)
Relay Output(available for CD-200)
Contract Rating
1A/120VAC or 1A/24VDC
Configuration
SPST, Normally Open relay
Relay Activated
On ≥ 1,000ppm,
Relay Deactivated
Off ≤900ppm
Relay on signal is designed to be activated
when CO2 measured value surpass 1,000ppm
and deactivated down to 900 ppm to avoid
unwanted rapid switching by hysteresis effect.
Relay activation and deactivation point could
be changed on sale as option.
Option 1.
Relay Activated & Deactivated
On ≥ 900ppm, Off ≤800ppm
OFF
(PPM)
ON
CO2
Relay Signal
Low
900
1,000
Hysteresis
High
Edaphic Scientific Pty Ltd