Specifications 

General Performance 

Operating Temperature range 

0 ~ 50℃ 

Operating Humidity range 

0 ~ 95% RH (Non-condensing) 

Storage Temperature 

-20℃ ~60℃

CO₂ Measurement 

Sensing Method 

NDIR (Non-dispersive Infrared) 

Measurement Range 

0 to 5,000 / 10,000ppm (Selectable by jumper), 
0 to 2,000 (Optional) 

Accuracy 

±30ppm ±5% 

Response Time(90%) 

150 seconds 

Sampling Interval 

3 sec. 

Electrical Data 

Input Power 

24VAC, 24VDC± 20%, 50/60Hz 
(2 Power lines) 

OutputConnector 

4 ~ 20mA and 2 ~ 10VDC (Default)

 

0 ~ 10VDCand 0 ~ 20mA

 

(Jumper selectable 

-Voltage output or current output)

Relay Output(available for CD-200) 

Contract Rating     

1A/120VAC or 1A/24VDC 

Configuration 

SPST, Normally Open relay 

Relay Activated   

On ≥ 1,000ppm, 

Relay Deactivated

 

Off ≤900ppm 

 

Relay on signal is designed to be activated 
when CO2 measured value surpass 1,000ppm 
and deactivated down to 900 ppm to avoid 
unwanted rapid switching by hysteresis effect. 

Relay activation and deactivation point could 
be changed on sale as option. 

Option 1.   

Relay Activated & Deactivated 

On ≥ 900ppm, Off ≤800ppm 

OFF

(PPM)

ON

CO2 

 

Relay Signal

Low

900

1,000

Hysteresis