2. Mounting
2.
Mounting
2.1. Installing the device
The multicontrol device must be installed on a horizontal and solid floor and it must be set up
vertically by using the adjustable stands (1). The four holes on side of the socket can be used to
transport the device (for example by inserting 2 pipes, max. 1").
figure
adjustable stands and transportation example
1:
The implementation into the system return must be executed acc. to the hydraulic diagrams in
chapter 3 - ”Hydraulic diagrams”.
multicontrol modular
series devices can be used in plants with max. temperature of 70 °C
MCM
at the connection point. If the max. temperature at the connection point exceeds 70 °C, EV
cooling vessels must be installed!
The implementation into the system return must be done at a position where no external
pressure can occur. External pressures could affect the trouble-free operation of the pressure
maintenance device.
NOTE!
For detailled information about hydraulic connection of multicontrol modular MCM
and
(Z)-M expansion vessels see chapter 8.
EG
i
INFORMATION!
Dimensioning of the expansion pipe according to
H 5151-1, see appendix A in
ÖNORM
instruction manual multicontrol
,
-_1. With multicontrol modular
all the
MCK MCM
MCM
piping must be made on-site according to the appropriate hydraulic diagram in chapter 3.