Quick Start Guide

Attach the Brackets

1.

Attach each of the front- and rear-post brackets to the switch 
using four of the included bracket screws.

2.

Use the screws and cage/clip nuts supplied with the rack to 
secure the switch in the rack. 

Adjust Rear-Post Bracket Ears

1.

Lock the position of the rear-post bracket ears using the included 
position-locking screws.

You can adjust the rear-post bracket ears to fit different rack 
depths from 56 cm to 75 cm.

Ground the Switch

1.

Ensure the rack is properly grounded and in compliance with 
ETSI ETS 300 253. Verify that there is a good electrical 
connection to the grounding point on the rack (no paint or 
isolating surface treatment).

Warning:

 

For a safe and reliable installation, use only 

the accessories and screws provided with the AS7326-
56X. Use of other accessories and screws could result in 
damage to the unit. Any damages incurred by using 
unapproved accessories are not covered by the warranty.

Avertissement:

 

Pour une installation sûre et fiable, 

utilisez uniquement les accessoires et les vis fournies avec 
le AS7326-56X. L’utilisation d’autres accessoires et vis 
pourrait endommager l’appareil. Les dommages causés 
par l’utilisation d’accessoires non approuvés ne sont pas 
couverts par la garantie.

Caution: 

The device must be installed in a restricted-

access location.

Attention:

 le périphérique doit être installé dans un 

emplacement à accès restreint.

Caution: 

The switch includes plug-in power supply (PSU) 

and fan tray modules that are installed into its chassis. All 
installed modules must have a matching airflow direction. 
That is, if the installed power modules have a front-to-back 
(F2B) airflow direction, all the installed fan tray modules 
must also have a F2B airflow direction.

Attention:

 Le commutateur comprend des modules 

d'alimentation et de bac de ventilateurs installés sur son 
châssis. Tous les modules installés doivent avoir une 
direction de circulation d'air correspondante. C'est-à-dire 
que tous les modules doivent avoir la même direction de 
circulation d'air : avant vers arrière (F2B), ou arrière vers 
avant (B2F).

Note:

 The switch has the Open Network Install 

Environment (ONIE) software installer pre-loaded on the 
switch, but no switch software image. Information about 
compatible switch software can be found at 

www.edge-core.com

.

1

1

1

2

Caution:

 Installing the switch in a rack requires two 

people. One person should position the switch in the rack, 
while the other person secures it using the rack screws.

Attention:

 Deux personnes sont nécessaires pour installer 

un commutateur dans un bâti : La première personne va 
positionner le commutateur dans le bâti, la seconde va le 
fixer avec des vis de montage.

2

1

3

1

2

E092019-CS-R03

150200001993A

www.edge-core.com

56-Port 25G/100G Top-of-Rack Switch

AS7326-56X

1.

25G/100G Top-of-Rack switch AS7326-56X

2.

Rack Mounting Kit—2 front-post brackets, 2 rear-post 
brackets, 20 screws, and 2 ear-locking screws

3.

Power cord (included with AC PSUs only)

4.

DC power connector (included with 48 VDC PSU only)

5.

Ground wire (included with DC PSUs only)

6.

Console cable—RJ-45 to DB-9

7.

Dust Cover Kit—8 for QSFP28 ports and 50 for SFP28 ports

8.

Documentation—

Quick Start Guide

 (this document) and 

Safety and Regulatory Information

1

Package Contents

2

3

4

7

8

5

6

Summary of Contents for AS7326-56X

Page 1: ...alled modules must have a matching airflow direction That is if the installed power modules have a front to back F2B airflow direction all the installed fan tray modules must also have a F2B airflow direction Attention Le commutateur comprend des modules d alimentation et de bac de ventilateurs installés sur son châssis Tous les modules installés doivent avoir une direction de circulation d air co...

Page 2: ...OS software image Subsequent switch boots will bypass ONIE and directly run the NOS software Connect Network Cables 1 For the RJ 45 Management port connect 100 ohm Category 5 5e or better twisted pair cable 2 Connect DAC cables to the SFP28 QSFP28 slots Or first install SFP28 QSFP28 transceivers in the slots and then connect fiber optic cabling to the transceiver ports 3 As connections are made ch...

Page 3: ...F Storage 40 C to 70 C 40 F to 158 F Humidity Operating 5 to 95 non condensing Power Consumption 550 Watts maximum AC PSU Power Rating 100 240 VAC 50 60 Hz 650 Watts AC Input 100 240 VAC 50 60 Hz 6 A maximum 48 VDC PSU Power Rating 48 VDC 650 Watts DC Input 36 V 72 V 16 A maximum Regulatory Compliances Emissions EN 55032 2015 AC 2016 Class A EN 61000 3 2 2014 Class A EN 61000 3 3 2013 FCC Class A ...

Page 4: ...以及安装在其机 箱中的风扇架模块 所有已安装模块都要求合适的气流 方向 即 如果安装的电源模块有从前到后 F2B 的气 流通过 则所有安装的风扇架模块也必须有 F2B 气流通 过 注意 本交换机上已预装了 Open Network Install Environment ONIE 软件安装程序 但没有交换机软件 映像 在以下网站可以找到有关兼容交换机软件的信息 www edge core com 小心 将此交换机安装在机架中时需要两个人 一个人应 在机架中托住交换机 另一个人使用机架螺丝固定它 1 1 1 2 小心 必须在所有电源连接都断开的情况下才能移除接地 连接 2 1 3 1 2 E092019 CS R03 150200001993A www edge core com 1 25G 以太网交换机 AS7326 56X 2 机架安装套件 2 个前柱支架 2 个后柱支架 20 个螺 丝...

Page 5: ...待 ONIE 软件找到和执行 NOS 安装程序 然 后等待安装程序加载 NOS 软件映像 以后交换机启动时将跳过 ONIE 而直接运行 NOS 软件 连接网线 1 对于RJ 45管理端口 连接100欧姆5 5e类或以上的双绞线 2 将 DAC 线连接到 SFP28 QSFP28 插槽 或者先将 SFP28 QSFP28 收发器安装到插槽 然后将光缆连接到收发器端 口 3 建立连接后 检查端口状态 LED 确保连接正常 对于 SFP28 端口 绿色 25 Gbps 模式 黄色 10 Gbps 模式 每个 QSFP28 端口有四个 LED 在以下模式中指示正常连接 1 LED 绿色 100 Gbps 模式 1 LED 蓝色 40 Gbps 模式 1 4 LED 黄色 25 Gbps 突破模式 四通道 1 4 LED 紫色 10 Gbps 突破模式 四通道 小心 使用 UL IEC EN 609...

Page 6: ... AC PSU 电源额定值 100 240 VAC 50 60 Hz 650 W 交流输入 100 240 VAC 50 60 Hz 6 A 最大 48 VDC PSU 电源额定值 48 VDC 650 W 直流输入 36 V 72 V 最大 16 A 管制符合性 辐射 EN 55032 2015 AC 2016 A 级 EN 61000 3 2 2014 A 级 EN 61000 3 3 2013 FCC A 级 VCCI A 级 CCC GB 9254 2008 A 级 BSMI A 级 CNS 13438 抗干扰性 EN 55024 2010 A1 2015 IEC 61000 4 2 3 4 5 6 8 11 安全 UL CSA 22 2 No 60950 1 UL60950 1 CB IEC EN60950 1 CCC GB4943 1 2011 BSMI CNS 14336 1...

Page 7: ...含安裝在其機箱中的插入式電源 PSU 和風扇托盤模組 所有已安裝之模組氣流方向 必須一 致 亦即 若已安裝之電源模組具有從前到後 F2B 氣 流方向 則所有已安裝之風扇托盤模組也必須具有 F2B 氣流方向 說明 交換器上有預載入的開放網路安裝環境 ONIE 軟體安裝程式 但沒有交換器軟體映像檔 關於相容交 換器軟體的資訊可參閱 www edge core com 注意 需要兩個人 將交換器裝到機櫃上 一個人應將交 換器放到機櫃中 而另一個人使用機櫃螺絲將其固定 1 1 1 2 注意 在切斷所有電源接線前 不得移除接地連接 2 1 3 1 2 E092019 CS R03 150200001993A www edge core com 1 25G 乙太網路交換器 AS7326 56X 2 機櫃安裝套件 2 個前柱托架 2 個後柱托架 20 個螺絲 和 2 個固定片鎖定螺絲 3 電源線 僅 A...

Page 8: ... NOS 安裝程式 並 等待安裝程式載入 NOS 軟體映像檔 之後交換器啟動時 會跳過 ONIE 直接運行 NOS 軟體 連接網路線 1 使用 100 ohm 第 5 類 5e 類或更優之雙絞線電纜 連接至 RJ 45 管理埠 2 連接 DAC 電纜至 SFP28 QSFP28 插槽 或先將 SFP28 QSFP28 收發器裝到插槽中 然後連接光纖電纜至收發器 埠 3 連接完成後 請檢查連接埠狀態 LED 確保連結有效 SFP28 連接埠 綠色 25 Gbps 模式 黃色 10 Gbps 模式 每個 QSFP28 連接埠有四個 LED 可指出在以下模式中的有 效連結 1 個 LED 亮綠光 100 Gbps 模式 1 個 LED 亮藍光 40 Gbps 模式 1 4 個 LED 亮黃光 25 Gbps 突圍模式 四道 1 4 個 LED 亮紫光 10 Gbps 突圍模式 四道 注意 使用 ...

Page 9: ...z 650 瓦 AC 輸入 100 240 VAC 50 60 Hz 最大 6 A 48 VDC PSU 額定功率 48 VDC 650 瓦 DC 輸入 36 V 72 V 最大 16 A 法規符合性 排放 EN 55032 2015 AC 2016 等級 A Class A EN 61000 3 2 2014 等級 A Class A EN 61000 3 3 2013 FCC 等級 A Class A VCCI 等級 A Class A CCC GB 9254 2008 等級 A Class A BSMI 等級 A Class A CNS 13438 電磁耐受性 EN 55024 2010 A1 2015 IEC 61000 4 2 3 4 5 6 8 11 安全性 UL CSA 22 2 No 60950 1 UL60950 1 CB IEC EN60950 1 CCC GB4943...

Reviews: