4 COMMUNICATIONS FOR SGC195 DEVICES
4 COMMUNICATIONS FOR SGC195 DEVICES
The
SGC195
device has the RTU unit
iGRID T&D iRTU
integrated. It has an Ethernet port and until two
communication independent ports ready to connect to the control center and/or others devices.
Furthermore it has a maintenance port miniUSB and other for USB keys.
Communications configuration of the device can be as follows and each available ports will be:
COM1
COM4
ETH
miniUSB
1TP
2TP
Table 4: Available ports in the SGC195 devices.
4.1 COM1 PORT
COM1
is a RS232(modem RS232)/RS422/RS484 software configurable port with 3kV isolated that
connects the SGC195 device with the either control center or other communication devices.
1.1 PROTOCOL AND CONNECTIONS
Data transmission to the control center can be configured by using any of the following protocols:
•
IEC60870-5-101
•
DNP3.0
•
Modbus RTU.
In addition it can be connected to a communicable device by using any of the next protocols:
•
IEC60870-5-101
•
Modbus RTU
•
DLMS
•
Procome.
To connect with the communication COM1 unit a connector Phoenix Contact model MC1.5/9-G-3.5 of 9
contacts is used with the next configuration:
00110E4
12
Summary of Contents for SGC Series
Page 31: ...6 FUNCTIONS 00110E4 EDP 26 Illustration 8 VPD unit logic diagram ...
Page 53: ...10 SCHEMATICS 10 SCHEMATICS 00110E4 EDP 48 ...
Page 54: ...SGC 49 EDP 00110E4 ...
Page 55: ...10 SCHEMATICS 00110E4 EDP 50 Illustration 13 Connection diagram ...
Page 56: ...SGC Illustration 14 SGC195 Connection diagram 51 EDP 00110E4 ...
Page 58: ...SGC 11 SIZE 53 EDP 00110E4 Drawing 1 Front and side views of SGC180 and SGC195 devices ...
Page 59: ...11 SIZE Drawing 2 Top and bottom view of SGC180 device 00110E4 EDP 54 ...
Page 60: ...SGC Drawing 3 Top and bottom view of SGC195 device 55 EDP 00110E4 ...