SGC
6.1.2 SIGNALS
OUTPUTS
Pickup
The current is above the pickup threshold
Pickup Phase
The phase current is above the pickup threshold
Pickup Neutral
The neutral current is above the pickup threshold
Trip
Tripping order to the circuit breaker
Trip 51
Tripping order from function 51
Trip 51N
Tripping order from function 51N
Trip 50
Tripping order from function 50
Trip 50N
Tripping order from function 50N
Blocked
The unit is in blocked state
MEASUREMENTS
Value peak pickup phases
Gives the maximum value of a phase pickup process
Value peak pickup neutral
Gives the maximum value of a neutral pickup process
COMMANDS
Pickup Signal Reset
Resets the pickup signalization
INPUTS
Block
The unit is disabled
Direction
The unit will only trip when the directional module allows it.
Table 24: Protection function signals 50/51/50N/51N