51/51N FUNCTION
Definite time:
Trip order is done when the line current exceeds the threshold during more than an adjustable time.
Inverse time:
The inverse time characteristic is determined by the following equation:
The K and n values for each curve family are:
•
N.I.: Normal Inverse (K=0.14 y n= 0.02).
•
V.I.: Very Inverse (K=13.5 y n=1).
•
E.I.: Extremely Inverse (K=80 y n=2).
•
D.T.: Definite time.
•
DI: Disabled.
37
00110E4
t =
K
I
I a
( )
n
- 1
Where:
I= Line current (A)
Ia= Pickup current (A)
t = Time (s)