12 TESTINGS
12 TESTINGS
●
Dielectric strength: 2kV / 50Hz 1 min. according UNE EN 60255-5.
●
Surge: 5kV 1,2/50us according UNE EN 60255-5.
●
Electrical disturbance testing: 2.5kV longitudinal / 1kV cross, class III according UNE 21136-22-1.
●
Fast transient: 2kV according UNE EN 61000-4-4 class III.
●
UNIPEDE ref NORM (SPEC) 13. “Automation and Control Apparatus for Generating Stations and
Substations – Electromagnetic Compatibility Requirements”.