EDS - TECHNICAL INSTRUCTIONS
3
QUICK INSTALLATION
The procedure below is intended for trained personell with previous experience in installing EDS Beam Smoke Detectors RK100R(S).
If you don’t have the needed experience please refer to the standard installation procedure of this manual. On our site
www.eds.eu
is available a video with instructions for installing the RK100R-S.
1 - fix the RK100-R detector and FX reflector
2 - connect the cables
3 - set JP2-JP3-JP4-JP5-JP7 detector’s jumpers (see pag.10)
4 - perfom the optical allignment with the Laser Pointer BLP-100 with the procedure set out in Chapter 7
5 - set SW3 selector on the device according to the distance between Detector and FX (see table in fig.7)
6 - place jumper JP1 in “ON” position (Alignment) and power up the device
7 - optimize the device signal using:
• the P1 trimmer
• the adjustment screws V1-V2-V3 on the optical block
• a multimeter (or the STS01 instrument)
• blue/Red Led signal level indication (fig.8 board)
8 - regulate the signal between 4,7V and 5V with the P1 trimmer
9 - verify the functioning obcuring the FX
10 - select the desired sensitivity of the Obscuration circuit with the SW2 selector (40-50-60-70%)
11 - select the desired sensibility of the Turbulence (Heat) circuit with the SW1 selector (if used - not present in -S
version)
12 - set JP1 in “OFF” position to activate the device
13 - close the cover within 5 minutes
14 - wait at least 5 minutes for the device to become operational
15 - perform operational tests