EDS - RK90R - OPTICAL BEAM SMOKE DETECTOR - USER GUIDE
20
18 -TECHNICAL DATA
• Model: RK90R
• Type: Reflective type Optical Beam Smoke Detector
• Manufacturer: EDS srl - V. Cà Nova Zampieri 6 - 37057 S.G. Lupatoto - Verona - ITALY
• Power Supply Range: 11- 30 Vdc
• Optical Path Lenght:
3 - 12 m with FX-07 reflector
10 - 25 m with FX-01 reflector
20 - 40 m with FX-02 reflector
25 - 50 m with FX-03 reflector
• Max. covered area: 750 mq
• Protection against the inversion of polarity
• Digitally codified infrared beam
• Power Consumption:
18,6 mA in normal operation
34 mA with the alarm relay activated
34 mA with the turbulence relay activated
50 mA with both alarm and fault relay activated
• Maximum angular missallignment of the detector: +/- 0,2°
• Maximum angular missallignment of the reflector: +/- 0,2°
• Selection of the obscuration alarm threshold level with a 4 positions switch:
position 1 - 70%
position 2 - 60%
position 3 - 50%
position 4 - 40%
• Selection of the turbulence alarm threshold level with a 4 positions switch
• Alarm Relay activation delay: 10 s
• Fault Relay activation delay: 5 s
• Detector's recovery time with alarm memory deactivated: about 5 s
• Detector's recovery time with alarm memory activated: about 5 s (power supply off)
• Working temperature: -10 + 55°C
• Red LED indication: alarm status
• Blue LED indication: compensation limit, interrupted beam, fault
• Alarm Relay: 1A/24 V dc
• Turbulence Relay: 1A/24 V dc
• Fault/Maintenance Relay: 1A/24 V dc
• 0-5 V Analog Output for signal level measuring/visualization
• Dimensions: 162 x 62 x 62 mm.
• Housing: autoextinguishing policarbonate box
• Relevant Standard: EN 54-12
• Certifications: EN54-12/CPD (0786-CPD-20803), VDS2504-VDS2344 (G209131)
• Protection Index: IP 50 (IEC 529-144)
• Weight: 200 gr.