SPM-010 Sump Pump Monitor and Control Unit
EDSPN: 2052102004
© Copyright 2022 Electronic Design Service, LLC All Rights Reserved
Page 15
WS-010 (with SIP) and SPM-010 Installation Instruction
1.
Find the SIP installation location. The location shall meet the following criteria:
a)
Be far enough from sump pump switch and pump
b)
Be installed at deepest area
2.
Measure external diameter (Dext) of SIP and drill mounting hole (hole diameter is Dext) in the
chosen cover installation area.
3.
Measure the Lsump (see Figure 6) and keep record.
4.
Cut SIP bottom edge as shown on Figure 6.
5.
Cut SIP to adjust length approximately 1
” to
2
” above the cover level
(L_SIP = Lsump +
2”)
. Where Hcover is thickness of cover.
6.
Install SIP into the mounting hole in the way when cut edge is connected to bottom of sump and
seal the sump cover area of installation hole by using any plumbing caulk.
7.
Install WS-010 sensor inside of SIP until lightly touching the bottom.
8.
Install SPM-010 in accordance with SPM-010 Installation section.
9.
Connect system in accordance with Figure 6 and Figure 4.
NOTE: DO NOT CUT OR INCREASE WIRE SENSOR LENGTH!