background image

Quext Smart Thermostat and Lock 

Installation Guide 

B.  Using a volt meter, test the power to the mounting plate between R and C terminals. The power must be 

between 24V and 30V. If it’s not between 24V and 30V, perform a pull test to confirm that the common wire 

is connected and troubleshoot accordingly.

7.  Install the Batteries

A.  Put the AA batteries in the Quext Smart Thermostat.

B.  Confirm that the Quext Smart Thermostat is powered by the batteries. 

The unit should show temperature and LoRa start to connect. The 

network connection icon will begin to flash on the thermostat.

8.  Install and Test the Quext Smart Thermostat

A.  Secure the Quext Smart Thermostat on the mounting plate. Do not 

press hard, it should easily snap into place.

B.  Turn the Quext Smart Thermostat to heat mode at two or more degrees below the measured point, and 

verify that warm air is coming out of the vents. Turn the Quext Smart Thermostat to AC mode at two or 

more degrees below the measured point, and verify that cool air is coming out of the vents. If the air is not 

warm or cold, check for possible loose connection with the wiring (refer to Troubleshooting FAQs.

C.  Confirm that the LoRa symbol displays on the Quext Smart Thermostat.  

If it does not, there may be a connection issue.  

Refer to Troubleshooting FAQs.

D.  Look at the face and observe the power.

 

▪ If no battery symbol is displayed either flashing or solid: 24V is present 

and batteries are good.

 

▪ If a flashing battery symbol is present: 24V is not present, but 

the batteries are good. To troubleshoot the 24V power, refer to 

Troubleshooting FAQs.

 

▪ If solid battery symbol is present: 24V is present, but the batteries are 

low and need to be replaced.

9.  Set the Quext Smart Thermostat

A.  Set the thermostat to the temperature you recorded at Step 2A. If you need help, refer to the 

IoT Resident 

User Manual

.

10.  Assign the Thermostat in the Database

A.  Go to the Quext IoT Web App.

B.  Select the 

Site Management tab, then select Thermostats.

C.  Select the desired thermostat (Dev UI/serial number should 

match the number in the database).

D.  In the detailed view, select 

Select Location

E.  Select the desired building and the desired unit, then select 

Done.

F.  Select 

Save.

Summary of Contents for quext iot

Page 1: ...Installation Manual...

Page 2: ...l Information 4 What s in the Box 4 Tools and Documents Required 4 Thermostat overview 4 Indicators 5 Thermostat Installation Steps 6 Wiring Connections 8 Troubleshooting and FAQs 9 Steps to Test Quex...

Page 3: ...Quext Smart Thermostat and Lock 3 Installation Guide Thermostat Installation...

Page 4: ...AA Batteries x8 Screws x4 Drywall Anchors x8 Tools and Documents Required Pencil Level Flathead Screwdriver 2 Phillips Screwdriver Smartphone Volt Meter Temperature Gun Community Installation Plan Io...

Page 5: ...s turned off Property control mode contact Property Management Power issue contact Property Management Solid AA batteries low Flashing 24V power not present System mode Fan mode AUTO The fan operates...

Page 6: ...he breaker panel If you cannot determine which breakers belong to the HVAC system notify the resident if home then turn off the main circuit breaker c Confirm that the power is off by attempting to ac...

Page 7: ...cool air is coming out of the vents If the air is not warm or cold check for possible loose connection with the wiring refer to Troubleshooting FAQs c Confirm that the LoRa symbol displays on the Que...

Page 8: ...Installation Guide Wiring Connections Terminal Conventional 1 Stage Heating 1 Stage Cooling R 24VAC Power from Heating Transformer Rc Not Used Y Compressor Relay C 24VAC Common Wire W Heat Relay G Fa...

Page 9: ...me Note the desired setpoint temperature should be set a minimum of 2 degrees above the ambient temperature for the Heating cycle to be initiated f The Mode icon should then appear in the upper left q...

Page 10: ...t f Set the meter to read AC voltage g Measure voltage between G Fan and C common This measurement should nominally measure as 24 volts Regulatory Information Per FCC 15 19 a 3 and a 4 this device com...

Page 11: ...Quext Smart Thermostat and Lock 11 Installation Guide Patent Numbers 10825273 10803685 10912370...

Reviews: